Addr.
Parameter
C
Setting Options
Default Setting
Supv. sum I
_:2431:1
Supv. sum I:Mode
•
off
•
on
•
test
off
_:2431:102
Supv. sum I:Threshold
1 A @ 100 Irated 0.030 A to 10.000 A
0.100 A
5 A @ 100 Irated 0.15 A to 50.00 A
0.50 A
1 A @ 1.6 Irated
0.001 A to 1.600 A
0.100 A
5 A @ 1.6 Irated
0.005 A to 8.000 A
0.500 A
_:2431:101
Supv. sum I:Slope factor
0
.
0
0
t
o
0
.
9
5
0
.
1
0
_:2431:6
Supv. sum I:Delay failure indi-
cation
0
.
0
0
s
t
o
1
0
0
.
0
0
s
5
.
0
0
s
Supv.ADC sum I
_:2401:1
Supv.ADC sum I:Mode
•
off
•
on
•
test
off
Measuring Point I-1ph
Addr.
Parameter
C
Setting Options
Default Setting
General
_:2311:101
General:Rated primary
current
1.0 A to 100000.0 A
1000.0 A
_:2311:102
General:Rated secondary
current
•
1 A
•
5 A
1 A
_:2311:103
General:Current range
•
1.6 x IR
•
100 x IR
100 x IR
_:2311:104
General:Internal CT type
•
CT protection
•
CT measurement
•
CT Process bus
CT protection
_:2311:116
General:Term. 1,3,5,7 in
dir. of obj.
•
no
•
yes
yes
Power-System Data
5.8 Settings
SIPROTEC 5, Fault Recorder, Manual
127
C53000-G5040-C018-5, Edition 11.2017
Содержание SIPROTEC 5
Страница 8: ...8 SIPROTEC 5 Fault Recorder Manual C53000 G5040 C018 5 Edition 11 2017 ...
Страница 18: ...18 SIPROTEC 5 Fault Recorder Manual C53000 G5040 C018 5 Edition 11 2017 ...
Страница 134: ...134 SIPROTEC 5 Fault Recorder Manual C53000 G5040 C018 5 Edition 11 2017 ...
Страница 212: ...212 SIPROTEC 5 Fault Recorder Manual C53000 G5040 C018 5 Edition 11 2017 ...
Страница 422: ...422 SIPROTEC 5 Fault Recorder Manual C53000 G5040 C018 5 Edition 11 2017 ...
Страница 426: ...426 SIPROTEC 5 Fault Recorder Manual C53000 G5040 C018 5 Edition 11 2017 ...
Страница 452: ...452 SIPROTEC 5 Fault Recorder Manual C53000 G5040 C018 5 Edition 11 2017 ...
Страница 490: ...490 SIPROTEC 5 Fault Recorder Manual C53000 G5040 C018 5 Edition 11 2017 ...