[scautcp3-220114-01-DE, 1, en_US]
Figure 6-68
SUP Ethernet Protocol Activation (base module)
With the selection of the SUP protocol for the RTD unit, DIGSI automatically adds the Analog units function
group and the RTD unit Ether. function to your device configuration (refer to the following figure).
[scauser6-190214-01, 1, en_US]
Figure 6-69
Analog Unit Instance
Now, set the port over which the SUP protocol runs. In addition, set the IP address of the RTD box (refer to the
following figure). This address must be set with the same value in the RTD box.
[scautcp5-220114-01-DE, 1, en_US]
Figure 6-70
Setting the Port and IP Address
Function-Group Types
6.5 Function-Group Type Analog Units
210
SIPROTEC 5, Fault Recorder, Manual
C53000-G5040-C018-5, Edition 11.2017