Logic
[locbsymm-100611-01.tif, 3, en_US]
Figure 8-17
Logic Diagram of the Current-Balance Supervision
The
Threshold min/max
parameter is the criterion by which unbalance in the phase currents is measured.
The device calculates the ratio between the minimum (I
min
) and the maximum (I
max
) phase current.
Enter the lower limit of the maximum phase current (I
max
) with the parameter
Release threshold
. This
specifies the lower limit of the operating range of this function.
Delay failure indication
If it falls below the balance factor
Threshold min/max
and at the same time the maximum phase current
exceeds the
Release threshold
, the operate delay of the failure indication (parameter
Delay failure
indication
) begins. If both conditions persist during this time, the indication
Failure
is generated.
Blocking the Function
The following blockings reset the picked up function completely:
•
Externally or internally via the binary input signal
>Block function
•
A protection pickup
The pickup signal of a protection function blocks the indication
Failure
.
Application and Setting Notes
Parameter: Threshold min/max
•
Recommended setting value
(_:102) Threshold min/max
=
0.5
The
Threshold min/max
parameter is used to set the ratio between the minimum (I
min
) and the maximum
(I
max
) phase current.
8.3.6.4
Supervision Functions
8.3 Supervision of the Secondary System
SIPROTEC 5, Fault Recorder, Manual
385
C53000-G5040-C018-5, Edition 11.2017
Содержание SIPROTEC 5
Страница 8: ...8 SIPROTEC 5 Fault Recorder Manual C53000 G5040 C018 5 Edition 11 2017 ...
Страница 18: ...18 SIPROTEC 5 Fault Recorder Manual C53000 G5040 C018 5 Edition 11 2017 ...
Страница 134: ...134 SIPROTEC 5 Fault Recorder Manual C53000 G5040 C018 5 Edition 11 2017 ...
Страница 212: ...212 SIPROTEC 5 Fault Recorder Manual C53000 G5040 C018 5 Edition 11 2017 ...
Страница 422: ...422 SIPROTEC 5 Fault Recorder Manual C53000 G5040 C018 5 Edition 11 2017 ...
Страница 426: ...426 SIPROTEC 5 Fault Recorder Manual C53000 G5040 C018 5 Edition 11 2017 ...
Страница 452: ...452 SIPROTEC 5 Fault Recorder Manual C53000 G5040 C018 5 Edition 11 2017 ...