Default setting
(_:9961:116) dM/dt drop hysteresis
=
0.980 p.u.
•
Default setting
(_:9961:112) Filter time
=
2 periods
With the
dM/dt drop active
parameter, you activate the gradient trigger in order to monitor the negative
gradients of the sum reactive power using the set filtering time (input in periods).
Parameter Value
Description
yes
The negative gradient of the sum reactive power is monitored.
no
The negative gradient of the sum reactive power is not monitored.
The hysteresis is preset at the factory to 0.980 p.u. (equal to 2 %) of the parameter
dM/dt drop (/Filter
time)
and can be adjusted.
Application and Setting Notes Trigger Ssum
Parameter: Mode
•
Default setting
(_:10021:1) Mode
=
off
With the
Mode
parameter, you activate the trigger for normal operation (On) or the test mode (Test).
Parameter Value
Description
on
The Trigger Ssum function block is activated and the sum apparent power
is monitored according to the set trigger parameters.
off
The Trigger Ssum function block is deactivated.
test
The Trigger Ssum function block is activated for test purposes.
Parameter: Max. Trigger Active/Max. Trigger/Max. Trigger Hysteresis
•
Default setting
(_:10021:101) Max. trigger active
=
yes
•
Default setting
(_:10021:105) Max. trigger
=
207.846 VA
•
Default setting
(_:10021:113) Max. trigger hysteresis
=
0.980 p.u.
With the
Max. trigger active
parameter, you activate the level trigger in order to monitor the sum
apparent power and to prevent it from exceeding the set values.
Parameter Value
Description
yes
The sum apparent power is monitored for exceeding the set values.
no
The sum apparent power is not monitored for exceeding the set values.
The hysteresis is preset at the factory to 0.980 p.u. (equal to 2 %) of the parameter
Max. trigger
and can
be adjusted.
Parameter: Min. Trigger Active/Min. Trigger/Min. Trigger Hysteresis
•
Default setting
(_:10021:102) Min. trigger active
=
yes
•
Default setting
(_:10021:106) Min. trigger
=
138.564 VA
•
Default setting
(_:10021:114) Min. trigger hysteresis
=
1.020 p.u.
With the
Min. trigger active
parameter, you activate the level trigger in order to monitor the sum
apparent power for dropping below the set values.
Parameter Value
Description
yes
The sum apparent power is monitored for dropping below the set values.
no
The sum apparent power is not monitored for dropping below the set
values.
The hysteresis is preset at the factory to 1.020 p.u. (equal to 2 %) of the parameter
Min. trigger
and can
be adjusted.
7.5.4.6
Fault Recorder
7.5 Trigger Functions 3-Phase
SIPROTEC 5, Fault Recorder, Manual
341
C53000-G5040-C018-5, Edition 11.2017
Содержание SIPROTEC 5
Страница 8: ...8 SIPROTEC 5 Fault Recorder Manual C53000 G5040 C018 5 Edition 11 2017 ...
Страница 18: ...18 SIPROTEC 5 Fault Recorder Manual C53000 G5040 C018 5 Edition 11 2017 ...
Страница 134: ...134 SIPROTEC 5 Fault Recorder Manual C53000 G5040 C018 5 Edition 11 2017 ...
Страница 212: ...212 SIPROTEC 5 Fault Recorder Manual C53000 G5040 C018 5 Edition 11 2017 ...
Страница 422: ...422 SIPROTEC 5 Fault Recorder Manual C53000 G5040 C018 5 Edition 11 2017 ...
Страница 426: ...426 SIPROTEC 5 Fault Recorder Manual C53000 G5040 C018 5 Edition 11 2017 ...
Страница 452: ...452 SIPROTEC 5 Fault Recorder Manual C53000 G5040 C018 5 Edition 11 2017 ...
Страница 490: ...490 SIPROTEC 5 Fault Recorder Manual C53000 G5040 C018 5 Edition 11 2017 ...