i
i
NOTE
The setting aid
Estimated record size
is dimmed and thus, you cannot set or change it.
Keep in mind that the estimation refers to typical sinusoidal signals and that the size of a fault record can
increase in the event of distorted signals.
i
i
NOTE
Due to the internal administration data, the complete flash memory size for the storing of recordings is not
available. The
Estimated record size
is user information in order to be able to estimate how many
recordings can be stored in the reserved flash memory. The actual size of the fault record depends on the
degree of compression and the number of stored events.
Parameter: Maximum Record Time
•
Default setting
(_:10741:111) Maximum record time
=
3.0 s
With the
Maximum record time
setting, you configure the maximum recording duration for a recording.
When the time configured expires, an ongoing fault recording is canceled. This parameter merely limits the
duration of the fault recording.
The maximum record duration includes the pre-trigger time.
i
i
NOTE
The parameter
Maximum record time
does not apply to fault records which are tripped by manual trig-
gers (
>Manual start
). For these fault records, the parameter
Manual record time
applies.
Parameter: Pre-Trigger Time
•
Default setting
(_:10741:112) Pre-trigger time
=
0.1 s
With the
Pre-trigger time
parameter, you configure the pre-trigger time for an individual fault
recording. The pre-trigger time defines that time before a trigger event.
i
i
NOTE
The
Pre-trigger time
must be a maximum of 10 % of the
Post-trigger time
, as otherwise
DIGSI 5 reports an inconsistency.
Parameter: Post-Trigger Time
•
Default setting
(_:10741:113) Post-trigger time
=
1.0 s
With the
Post-trigger time
parameter, you configure the post-trigger time for an individual fault
recording. The post-trigger time defines that time after dropout of the trigger event.
Parameter: Manual Record Time
•
Default setting
(_:10741:116) Manual record time
=
1.0 s
The parameter
Manual record time
determines the length of a recording if the fault recording is acti-
vated dynamically (edge-controlled) via a separately configured input signal
>Manual start
.
i
i
NOTE
The pre-trigger time, the post-trigger time, and the maximum record time have no effect in this case.
Fault Recorder
7.2 Function-Group Type Recorder
SIPROTEC 5, Fault Recorder, Manual
239
C53000-G5040-C018-5, Edition 11.2017
Содержание SIPROTEC 5
Страница 8: ...8 SIPROTEC 5 Fault Recorder Manual C53000 G5040 C018 5 Edition 11 2017 ...
Страница 18: ...18 SIPROTEC 5 Fault Recorder Manual C53000 G5040 C018 5 Edition 11 2017 ...
Страница 134: ...134 SIPROTEC 5 Fault Recorder Manual C53000 G5040 C018 5 Edition 11 2017 ...
Страница 212: ...212 SIPROTEC 5 Fault Recorder Manual C53000 G5040 C018 5 Edition 11 2017 ...
Страница 422: ...422 SIPROTEC 5 Fault Recorder Manual C53000 G5040 C018 5 Edition 11 2017 ...
Страница 426: ...426 SIPROTEC 5 Fault Recorder Manual C53000 G5040 C018 5 Edition 11 2017 ...
Страница 452: ...452 SIPROTEC 5 Fault Recorder Manual C53000 G5040 C018 5 Edition 11 2017 ...
Страница 490: ...490 SIPROTEC 5 Fault Recorder Manual C53000 G5040 C018 5 Edition 11 2017 ...