Addr.
Parameter
C
Setting Options
Default Setting
_:19411:106
Trigger P 1:Min. trigger
1 A @ 100 Irated 0.20 W to 20000.00 W
80.00 W
5 A @ 100 Irated 0.60 W to 100000.00 W
400.00 W
_:19411:114
Trigger P 1:Min. trigger
hysteresis
1.010 p.u. to 1.100 p.u.
1.020 p.u.
_:19411:103
Trigger P 1:dM/dt rise
active
•
no
•
yes
no
_:19411:107
Trigger P 1:dM/dt rise (/
Filter time)
1 A @ 100 Irated 0.20 W to 20000.00 W
20.00 W
5 A @ 100 Irated 0.60 W to 100000.00 W
100.00 W
_:19411:115
Trigger P 1:dM/dt rise
hysteresis
0.900 p.u. to 0.990 p.u.
0.980 p.u.
_:19411:104
Trigger P 1:dM/dt drop
active
•
no
•
yes
no
_:19411:108
Trigger P 1:dM/dt drop (/
Filter time)
1 A @ 100 Irated 0.20 W to 20000.00 W
20.00 W
5 A @ 100 Irated 0.60 W to 100000.00 W
100.00 W
_:19411:116
Trigger P 1:dM/dt drop
hysteresis
0.900 p.u. to 0.990 p.u.
0.980 p.u.
_:19411:112
Trigger P 1:Filter time
2 cycles to 250 cycles
2 cycles
Trigger Q 1
_:19441:1
Trigger Q 1:Mode
•
off
•
on
•
test
off
_:19441:111
Trigger Q 1:Power direc-
tion
•
negative
•
positive
positive
_:19441:101
Trigger Q 1:Max. trigger
active
•
no
•
yes
yes
_:19441:105
Trigger Q 1:Max. trigger 1 A @ 100 Irated 0.20 var to 20000.00 var
120.00 var
5 A @ 100 Irated 0.60 var to 100000.00 var
600.00 var
_:19441:113
Trigger Q 1:Max. trigger
hysteresis
0.900 p.u. to 0.990 p.u.
0.980 p.u.
_:19441:102
Trigger Q 1:Min. trigger
active
•
no
•
yes
yes
_:19441:106
Trigger Q 1:Min. trigger 1 A @ 100 Irated 0.20 var to 20000.00 var
80.00 var
5 A @ 100 Irated 0.60 var to 100000.00 var
400.00 var
_:19441:114
Trigger Q 1:Min. trigger
hysteresis
1.010 p.u. to 1.100 p.u.
1.020 p.u.
_:19441:103
Trigger Q 1:dM/dt rise
active
•
no
•
yes
no
_:19441:107
Trigger Q 1:dM/dt rise (/
Filter time)
1 A @ 100 Irated 0.20 var to 20000.00 var
20.00 var
5 A @ 100 Irated 0.60 var to 100000.00 var
100.00 var
_:19441:115
Trigger Q 1:dM/dt rise
hysteresis
0.900 p.u. to 0.990 p.u.
0.980 p.u.
_:19441:104
Trigger Q 1:dM/dt drop
active
•
no
•
yes
no
_:19441:108
Trigger Q 1:dM/dt drop (/
Filter time)
1 A @ 100 Irated 0.20 var to 20000.00 var
20.00 var
5 A @ 100 Irated 0.60 var to 100000.00 var
100.00 var
_:19441:116
Trigger Q 1:dM/dt drop
hysteresis
0.900 p.u. to 0.990 p.u.
0.980 p.u.
_:19441:112
Trigger Q 1:Filter time
2 cycles to 250 cycles
2 cycles
Fault Recorder
7.4 Trigger Functions 1-Phase
SIPROTEC 5, Fault Recorder, Manual
295
C53000-G5040-C018-5, Edition 11.2017
Содержание SIPROTEC 5
Страница 8: ...8 SIPROTEC 5 Fault Recorder Manual C53000 G5040 C018 5 Edition 11 2017 ...
Страница 18: ...18 SIPROTEC 5 Fault Recorder Manual C53000 G5040 C018 5 Edition 11 2017 ...
Страница 134: ...134 SIPROTEC 5 Fault Recorder Manual C53000 G5040 C018 5 Edition 11 2017 ...
Страница 212: ...212 SIPROTEC 5 Fault Recorder Manual C53000 G5040 C018 5 Edition 11 2017 ...
Страница 422: ...422 SIPROTEC 5 Fault Recorder Manual C53000 G5040 C018 5 Edition 11 2017 ...
Страница 426: ...426 SIPROTEC 5 Fault Recorder Manual C53000 G5040 C018 5 Edition 11 2017 ...
Страница 452: ...452 SIPROTEC 5 Fault Recorder Manual C53000 G5040 C018 5 Edition 11 2017 ...
Страница 490: ...490 SIPROTEC 5 Fault Recorder Manual C53000 G5040 C018 5 Edition 11 2017 ...