Time delay
0.00 s to 60.00 s
Increments of 0.01 s
Pickup delay
0.00 s to 320.00 s
Increments of 0.01 s
Dropout ratio
0.90 to 0.99
Increments of 0.01
V< faulty ph-gnd vltg.
0.300 V to 200.000 V
Increments of 0.001 V
V> healthy ph-gnd. vltg.
0.300 V to 200.000 V
Increments of 0.001 V
Dropout
The greater dropout differential (=
| pickup value – dropout value |
) of the following 2 criteria
applies:
Dropout differential derived from the parameter
Dropout ratio
If this parameter is not available, a dropout ratio of 95 % applies for the overvoltage and of 105 % for the
undervoltage functionality.
Minimum absolute dropout differential
150 mV sec.
Times
Operate time with time delay = 0 ms
Standard filter, true RMS
Approx. 25 ms + OOT
60
at 50 Hz
Approx. 22 ms + OOT at 60 Hz
2 cycle filters
Approx. 45 ms + OOT at 50 Hz
Approx. 39 ms + OOT at 60 Hz
Dropout time
Standard filter, true RMS
Approx. 20 ms + OOT at 50 Hz
Approx. 17 ms + OOT at 60 Hz
2 cycle filters
Approx. 31 ms + OOT at 50 Hz
Approx. 27 ms + OOT at 60 Hz
Frequency Operating Range
0.9 ≤ f/f
rated
≤ 1.1
According to specified tolerances
10 Hz ≤ f < 0.9 f
rated
1.1 f
rated
< f ≤ 90 Hz
Slightly expanded tolerances
f < 10 Hz
f > 90 Hz
Active
Tolerances
Voltages
0.5 % of the setting value or 0.05 V
Time delays
1 % of the setting value or 10 ms
60
OOT (Output Operating Time) additional delay of the output medium used, see chapter
Technical Data
12.10 Voltage Protection
SIPROTEC 5, Merging Unit 6MU85, Manual
837
C53000-G5040-C074-1, Edition 01.2020