Instantaneous Tripping at Switch onto Fault
Setting Values
Tripping delay
0.00 s to 60.00 s
Increments of
0.01 s
Tolerances
Times
< 1 % of the setting value or 10 ms
12.26
Technical Data
12.26 Instantaneous Tripping at Switch onto Fault
862
SIPROTEC 5, Merging Unit 6MU85, Manual
C53000-G5040-C074-1, Edition 01.2020