Voltage Protection
Overvoltage Protection with 3-Phase Voltage
Setting Values for the Function
Stabilization counter
0 to 10
Increments of 1
Setting Values for Stage Type Definite-Time Overvoltage Protection
Measured value
Phase-to-phase
Phase-to-ground
Method of measurement
Fundamental component
RMS value
Pickup mode
1 out of 3
3 out of 3
Pickup value
55
0.300 V to 340.000 V
Increments of 0.001 V
Time delay
0.00 s to 300.00 s
Increments of 0.01 s
Dropout ratio
0.90 to 0.99
Increments of 0.01
Setting Values for Stage Type Inverse-Time Overvoltage Protection
Measured value
Phase-to-phase
Phase-to-ground
Method of measurement
Fundamental component
RMS value
Pickup mode
1 out of 3
3 out of 3
Pickup value
0.300 V to 340.000 V
Increments of 0.001 V
Pickup factor
1.00 to 1.20
Increments of 0.01
Characteristic constant k
0.00 to 300.00
Increments of 0.01
Characteristic constant α
0.010 to 5.000
Increments of 0.001
Characteristic constant c
0.000 to 5.000
Increments of 0.001
Time multiplier
0.05 to 15.00
Increments of 0.01
Additional time delay
0.00 s to 60.00 s
Increments of 0.01 s
Reset time
0.00 s to 60.00 s
Increments of 0.01 s
Operate Curve for Stage Type Inverse-Time Overvoltage Protection
Where
T
op
Operate delay
T
inv
Inverse-time delay
T
add
Additional time delay (parameter
Additional time delay
)
12.10
12.10.1
55
If you have selected the method of measurement = RMS value, do not set the threshold value under 10 V.
Technical Data
12.10 Voltage Protection
SIPROTEC 5, Merging Unit 6MU85, Manual
833
C53000-G5040-C074-1, Edition 01.2020