Voltage-Jump Detection
Times
Pickup time
Approx. 10 ms + OOT
72
at 50 Hz
Approx. 8 ms + OOT at 60 Hz
Frequency Operating Range
0.9 ≤ f/f
rated
≤ 1.1
According to specified tolerances
10 Hz ≤ f < 0.9 f
rated
1.1 f
rated
< f ≤ 90 Hz
Slightly expanded tolerances
f < 10 Hz
f > 90 Hz
Inactive
Tolerances
Voltages
2 % of the setting value or 0.100 V
for amplitude changes of sinusoidal measurands
Pulse time
1 % of the setting value or 10 ms
12.16
72
OOT (Output Operating Time) additional delay of the output medium used, for example 5 ms with fast relays
Technical Data
12.16 Voltage-Jump Detection