External Trip Initiation
Setting Values
Tripping delay
0.00 s to 60.00 s
Increments of 0.01 s
Times
Operate time with time delay = 0 ms
- At initiation via binary input signal
Approx. 10 ms + OOT
70
.
Tolerance
Sequence tolerance for delay times
1 % of the setting value or 10 ms
12.13
70
OOT (Output Operating Time) additional delay of the output medium used, for example 5 ms with fast relays, see chapter
Technical Data
12.13 External Trip Initiation
848
SIPROTEC 5, Merging Unit 6MU85, Manual
C53000-G5040-C074-1, Edition 01.2020