Tolerances for Stage Type Inverse-Time Overvoltage Protection
Voltages
0.5 % of the setting value or 0.05 V
Operate time for
1.2 ≤ V/V threshold value ≤ 20
5 % of the setting value or 30 ms
Reset time delay
1 % of the setting value or 10 ms
Overvoltage Protection with Positive-Sequence Voltage
Setting Values
Pickup value
0.300 V to 200.000 V
Increments of 0.001 V
Time delay
0.00 s to 60.00 s
Increments of 0.01 s
Dropout ratio
0.90 to 0.99
Increments of 0.01
Dropout
The greater dropout differential (=
| pickup value – dropout value |
) of the following 2 criteria
applies:
Dropout differential derived from the parameter
Dropout ratio
If this parameter is not available, a dropout ratio of 95 % applies for the overvoltage and of 105 % for the
undervoltage functionality.
Minimum absolute dropout differential
150 mV sec.
Times
Operate time with time delay = 0 ms, typical
Approx. 25 ms + OOT
57
at 50 Hz
Approx. 22 ms + OOT at 60 Hz
Operate time with time delay = 0 ms, maximum
Approx. 30 ms + OOT at 50 Hz
Approx. 26 ms + OOT at 60 Hz
Dropout time, typical
Approx. 25 ms + OOT
Dropout time, maximum
Approx. 30 ms + OOT
Frequency Operating Range
0.9 ≤ f/f
rated
≤ 1.1
According to specified tolerances
10 Hz ≤ f < 0.9 f
rated
1.1 f
rated
< f ≤ 90 Hz
Slightly expanded tolerances
f < 10 Hz
f > 90 Hz
Active
Tolerances
Voltages
0.5 % of the setting value or 0.05 V
Time delays
1 % of the setting value or 10 ms
Overvoltage Protection with Negative-Sequence Voltage
Setting Values for the Function
Measuring window
1 cycle to 10 cycles
Increments of 1 cycle
12.10.2
12.10.3
57
OOT (Output Operating Time): additional delay of the output medium used, see Chapter
Technical Data