Setting Values
Pickup value of V2
0.300 V to 200.000 V
Increments of 0.001 V
Operate delay
0.00 s to 60.00 s
Increments of 0.01 s
Dropout ratio
0.90 to 0.99
Increments of 0.01
Dropout
The greater dropout differential (=
| pickup value – dropout value |
) of the following 2 criteria
applies:
Dropout differential derived from the parameter
Dropout ratio
If this parameter is not available, a dropout ratio of 95 % applies for the overvoltage and of 105 % for the
undervoltage functionality.
Minimum absolute dropout differential
150 mV sec.
Times
Pickup times
55 ms to 210 ms + OOT
58
(depends on the measuring-window length) at 50 Hz
48 ms to 185 ms + OOT
(depends on the measuring-window length) at 60 Hz
Dropout time
20 ms to 70 ms + OOT
(depends on the measuring-window length)
Frequency Operating Range
0.9 ≤ f/f
rated
≤ 1.1
According to specified tolerances
10 Hz ≤ f < 0.9 f
rated
1.1 f
rated
< f ≤ 90 Hz
Slightly expanded tolerances
f < 10 Hz
f > 90 Hz
Inactive
Tolerances
Voltages
0.50 % of the setting value or 0.050 V
Time delays
1.00 % of the setting value or 10 ms
Overvoltage Protection with Zero-Sequence Voltage/Residual Voltage
Setting Values
Method of measurement
RMS value
Fundamental component
Fundamental component
over 2 cycle filters
Block. on measuring-voltage outage
Yes
No
Determ. ph. aff. by grd. flt.
Yes
No
Threshold value
59
0.300 V to 340.000 V
Increments of 0.001 V
12.10.4
58
OOT (Output Operating Time): additional delay of the output medium used, for example 5 ms with fast relays
59
If you have selected the method of measurement = RMS value, do not set the threshold value under 10 V.
Technical Data
12.10 Voltage Protection
836
SIPROTEC 5, Merging Unit 6MU85, Manual
C53000-G5040-C074-1, Edition 01.2020