Analog-Units Function Group
20-mA Unit Ether. 7XV5674-0KK00-1AA1
Max. number of connected 20-mA units
4
Max. number of channels per 20-mA unit
12
20-mA Unit Serial 7XV5674-0KK30-1AA1 (RS485) and 7XV5674-0KK40-1AA1 (Fiberglass)
Max. number of connected 20-mA units
4
Max. number of channels per 20-mA unit
12
RTD Unit (Ziehl TR1200) 7XV5662-6AD10
Max. number of connected RTD units
4
Max. number of sensors per RTD unit
12
Sensor type
Pt 100 to EN 60751; connection of Ni 100 and Ni 120
sensors possible. The measured values must be
converted in the evaluation unit.
RTD Unit (Ziehl TR1200 IP) 7XV5662-8AD10
Max. number of connected RTD units
4
Max. number of sensors per RTD unit
12
Sensor type
Pt 100 to EN 60751; connection of Ni 100 and Ni 120
sensors possible. The measured values must be
converted in the evaluation unit.
Temperature Measured Values
Unit of measurement for temperature
°C or °F, adjustable
Pt 100
-199 °C to 800 °C (-326 °F to 1472 °F)
Ni 100
-54 °C to 278 °C (-65 °F to 532 °F)
Ni 120
-52 °C to 263 °C (-62 °F to 505 °F)
Resolution
1 °C or 1 °F
Tolerance
±0.5 % of the measured value ±1 K
12.31
Technical Data
12.31 Analog-Units Function Group
870
SIPROTEC 5, Merging Unit 6MU85, Manual
C53000-G5040-C074-1, Edition 01.2020