Protocol
DIGSI 5 protocol (secure Web service protocol)
IEC 61850 (MMS and GOOSE)
IEC 61850-8-1 (9-2 Client and 9-2 Merging Unit)
IEC 60870-5-104
You can switch other network services such as RSTP, PRP, SNTP, and
IEEE 1588v2/PTP on and off.
Max. line length
2 km for 62.5 µm/125 µm optical fibers
Transmitter Power
Minimum
Typical
Maximum
50 μm/125 μm, NA
28
= 0.2
-24.0 dBm
-21.0 dBm
-17.0 dBm
62.5 μm/125 μm, NA
28
= 0.275
-20.0 dBm
-17.0 dBm
-14.0 dBm
Receiver sensitivity
Maximum -12.0 dBm
Minimum -31.0 dBm
Optical budget
Minimum 7.0 dB for 50 μm/125 μm, NA
28
= 0.2
Minimum 11.0 dB for 62.5 μm/125 μm, NA
28
= 0.275
Interface design
Corresponds to IEEE 802.3, 100Base-FX
Laser class 1 as per EN 60825-1/-2
With the use of 62.5 μm/125 μm and 50 μm/125 μm optical fibers
i
i
NOTE
The firmware must be updated to version ≥ V7.90 if using the ETH-BD-2FO module. If the module is
connected to a device with a previous version, a hardware failure is reported that disappears with an FW
update to V7.90. As this is not an actual hardware failure, there is no need to send in the device.
The ETH-BD-2FO module offers the possibility of replacing the SFPs (Small Form-Factor Pluggable) delivered by
default for a communication route of up to 2 km by SFPs that can be ordered separately in order to adapt the
interface to different transmission media and longer routes.
SFP with Optical Interface for 24 km, Single Mode
Description
SFP for distances up to 24 km when using singlemode optical fibers
Product code
P1Zxxxxxxxxxx
Connector type
Duplex LC
Wavelength
λ = 1300 nm
Baud rate
100 Mbit/s
Protocol
See information for the module ETH-BD-2FO
Max. line length
24 km for 9 µm/125 µm optical fibers
Distance 24 km
Laser class 1 as per EN 60825-1/-2
With the use of 9 µm/125 µm optical fibers
Transmitter Power
Minimum
Maximum
Transmitter power coupled in
singlemode optical fibers
-15 dBm
-8 dBm
Receiver sensitivity
-8 dBm
-31dBm
Optical budget
16 dB
–
28
Numerical Aperture (NA = sin θ [launch angle])
Technical Data
12.1 General Device Data
796
SIPROTEC 5, Merging Unit 6MU85, Manual
C53000-G5040-C074-1, Edition 01.2020