SIPROTEC 5 Process-Bus Client
Supported Sampled-Value Streams for 50 Hz and 60 Hz Rated Power Frequency
Stream Type
Sampling Rate
ASDU
Analog Channels
IEC 61850-9-2 LE
80 samples/cycle
1
4 I, 4 V
IEC 61850-9-2 LE
256 samples/cycle
1
4 I, 4 V
IEC 61869-9
4000 Hz
1
Max. 32
IEC 61869-9
4800 Hz
1
Max. 32
IEC 61869-9
4800 Hz
2
Max. 32
IEC 61869-9
12 800 Hz
8
Max. 32
IEC 61869-9
15 360 Hz
8
Max. 32
Max. number of analog channels to be subscribed
(Limitations of the individual device applies and
supersede the max. usable analog channels)
60
Max. number of streams able to be subscribed per
ETH-BD-2FO
32
Max. number of ETH-BD-2FO with Process-Bus Client
functionality per SIPROTEC 5 device
4
Simultaneous support at same ETH-BD-2FO module of
•
IEEE 1588v2/PTP
•
GOOSE
•
Process-bus client functionality
YES
Simultaneous support at same ETH-BD-2FO module of
•
IEEE 1588v2/PTP
•
GOOSE
•
Merging Unit functionality
•
Process-bus client functionality
NO
Simultaneous support on different ETH-BD-2FO
module of
•
IEEE 1588v2/PTP (only on one ETH-BD-2FO)
•
GOOSE
•
Merging Unit functionality
•
Process-bus client functionality
YES
Use of IEC 61850-8-1 MMS and Reports with MU func-
tionality
NO
12.39
Technical Data
12.39 SIPROTEC 5 Process-Bus Client
882
SIPROTEC 5, Merging Unit 6MU85, Manual
C53000-G5040-C074-1, Edition 01.2020