Integrated Power Supply
Recommended external
protection
Miniature circuit breaker 6 A, characteristic C according to IEC 60898
Internal fuse
–
DC 24 V to DC 48 V
DC 60 V to DC 125 V
DC 24 V to DC 48 V
AC 100 V to AC 230 V
PS101
Only for non-modular
devices
4 A inert, AC 250 V,
DC 150 V,
UL recognized
SIBA type 179200 or
Schurter type SPT 5x20
2 A time-lag, AC 250 V, DC 300 V, UL recognized
SIBA type 179200 or Schurter type SPT 5x20
PS201, PS203, CB202
(to device version xA)
4 A inert, AC 250 V,
DC 150 V,
UL recognized
SIBA type 179200 or
Schurter type SPT 5x20
2 A time-lag, AC 250 V, DC 300 V, UL recognized
SIBA type 179200 or Schurter type SPT 5x20
PS201, PS203, PS204,
CB202
(Device version xB and
higher)
4 A inert, AC 250 V,
DC 150 V,
UL recognized
SIBA type 179200 or
Schurter type SPT 5x20
3.15 A time-lag, AC 250 V, DC 300 V, UL recognized
SIBA type 179200 or Schurter type SPT 5x20
Power consumption (life relay active)
–
DC
AC 230 V/50 Hz
AC 115 V/50 Hz
1/3 module, non-modular
Without plug-in modules
7 W
16 VA
12.5 VA
1/3 base module, modular
Without plug-in modules
13 W
55 VA
40 VA
1/6 expansion module
3 W
6 VA
6 VA
1/6 plug-in module
assembly without plug-in
modules (modules CB202)
3.5 W
14 VA
7 VA
Plug-in module for base
module or plug-in module
assembly (for example,
communication module)
< 5 W
< 6 VA
< 6 VA
Stored-energy time for auxiliary voltage outage or
short circuit, modular devices
IEC 61000-4-11
IEC 61000-4-29
For V ≥ DC 24 V ≥ 50 ms
For V ≥ DC 110 V ≥ 50 ms
For V ≥ AC 115 V ≥ 50 ms
Stored-energy time for auxiliary voltage outage or
short circuit, non-modular devices
IEC 61000-4-11
IEC 61000-4-29
For V ≥ DC 24 V ≥ 20 ms
For V ≥ DC 60 V ≥ 50 ms
For V ≥ AC 115 V ≥ 200 ms
Technical Data
12.1 General Device Data
SIPROTEC 5, Merging Unit 6MU85, Manual
791
C53000-G5040-C074-1, Edition 01.2020