SIPROTEC 5 Merging Unit Functionality
Supported Sampled-Value Streams for 50 Hz and 60 Hz Rated Power Frequency
Stream Type
Sampling Rate
ASDU
Analog Channels
IEC 61850-9-2 LE
80 samples/cycle
1
4 I, 4 V
IEC 61850-9-2 LE
256 samples/cycle
1
4 I, 4 V
IEC 61869-9
4000 Hz
1
Max. 32
IEC 61869-9
4800 Hz
1
Max. 32
IEC 61869-9
4800 Hz
2
Max. 32
IEC 61869-9
12 800 Hz
8
Max. 32
IEC 61869-9
15 360 Hz
8
Max. 32
i
i
NOTE
IEC 61869-9 limit of 24 analog channels is defined. This must be considered for third-party process-bus
clients.
Number of published streams per ETH-BD-2FO
1
Max. number of ETH-BD-2FO with MU functionality
per SIPROTEC 5 device
4
Simultaneous support at same ETH-BD-2FO module of
•
IEEE 1588v2/PTP
•
GOOSE
•
Merging Unit functionality
YES
Simultaneous support at same ETH-BD-2FO module of
•
IEEE 1588v2/PTP
•
GOOSE
•
Merging Unit functionality
•
Process-bus client functionality
NO
Simultaneous support on different ETH-BD-2FO
module of
•
IEEE 1588v2/PTP (only on one ETH-BD-2FO)
•
GOOSE
•
Merging Unit functionality
•
Process-bus client functionality
YES
Use of IEC 61850-8-1 MMS and Reports with MU func-
tionality
NO
12.40
Technical Data
12.40 SIPROTEC 5 Merging Unit Functionality
SIPROTEC 5, Merging Unit 6MU85, Manual
883
C53000-G5040-C074-1, Edition 01.2020