Configuring a further connection (such as HMI)
12
12.1
Rules for arranging modules in the HW Config
Slot rules
Modules must be inserted in the rack without gaps.
Exception:
Slot 3 remains empty in the configuration table. This slot is reserved.
Note
The actual arrangement has no gaps, as otherwise the bus on the backplane would be
interrupted.
Table 12-1
Slot rule for SIMOTION rack 0 (SIMOTION C only)
Slot 1:
Power supply only, PS 307 xA
Slot 2:
CPU only
Slot 3:
Empty or interface module
Slots 4 to 11:
I/O modules or empty
SIMOTION SCOUT provides the following support when you configure a station:
● A message will appear if, for example, a module cannot be inserted into the desired slot.
● Address areas are also checked to prevent dual allocation of addresses.
● The status bar or messages displayed provide feedback, which you should pay attention
to. Important information can also be found in the help.
● Temporary rules, that is, rules that apply only to a specific version, are not considered (such
as restriction of the useable slots due to a functional restriction for individual modules).
Consult the documentation or the current product information for the modules.
Note
Modules that are installed but not configured are repeatedly addressed via the PROFIBUS.
This requires additional computing time.
SIMOTION SCOUT
Configuration Manual, 11/2016
205
Содержание SIMOTION SCOUT
Страница 12: ...Preface 1 4 Hotline and Internet addresses SIMOTION SCOUT 12 Configuration Manual 11 2016 ...
Страница 32: ...Installation 4 4 Licenses SIMOTION SCOUT 32 Configuration Manual 11 2016 ...
Страница 64: ...User interface 5 11 Adding add ons to the workbench SIMOTION SCOUT 64 Configuration Manual 11 2016 ...
Страница 146: ...Configuring parameterizing 6 14 Writing the boot sector SIMOTION SCOUT 146 Configuration Manual 11 2016 ...
Страница 224: ...Product combinations 13 9 DCC programming system SIMOTION SCOUT 224 Configuration Manual 11 2016 ...
Страница 244: ...Index SIMOTION SCOUT 244 Configuration Manual 11 2016 ...