4. Assign the fault handling routines:
– In the tree of the execution system, select the branch ExecutionLevels >
OperationLevels > SystemInterruptTasks > TechnologicalFaultTask. Assign the MCC
program fault.technology_fault to this task.
– In the tree of the execution system, select the branch ExecutionLevels >
OperationLevels > SystemInterruptTasks > PeripheralFaultTask. Assign the MCC
program fault.peripheral_fault to this task.
5. Click Close. Confirm with Yes if you are prompted to save.
Result
The execution system is configured.
Loading the configured execution system to the target system
Save and compile the changes, go online and load the configured execution system into the
target system.
6.8
Project generator
6.8.1
Overview
With the project generator, you can quickly and easily create a new SIMOTION project or
update an existing project on the basis of templates.
The templates include preconfigured SIMOTION devices and modules, all of which are
supplied with the ProjectGenerator. These can be automatically integrated in a project with
the ProjectGenerator.
Overview of the ProjectGenerator functions
You can execute the following functions with the ProjectGenerator:
● Create a new project or open and edit an existing project
● Create a new device or open and edit an existing device
● Automatic configuration of the modules on the basis of the selected hardware
● Copy files/directories in the file system
● XML interface for user-specific expansions
– Generation of the user-interface elements
– Generic function calls
● Assign programs to the execution system
● FTP transport of files to the SIMOTION device (e.g. SIMOTION IT pages)
Configuring/parameterizing
6.8 Project generator
SIMOTION SCOUT
Configuration Manual, 11/2016
131
Содержание SIMOTION SCOUT
Страница 12: ...Preface 1 4 Hotline and Internet addresses SIMOTION SCOUT 12 Configuration Manual 11 2016 ...
Страница 32: ...Installation 4 4 Licenses SIMOTION SCOUT 32 Configuration Manual 11 2016 ...
Страница 64: ...User interface 5 11 Adding add ons to the workbench SIMOTION SCOUT 64 Configuration Manual 11 2016 ...
Страница 146: ...Configuring parameterizing 6 14 Writing the boot sector SIMOTION SCOUT 146 Configuration Manual 11 2016 ...
Страница 224: ...Product combinations 13 9 DCC programming system SIMOTION SCOUT 224 Configuration Manual 11 2016 ...
Страница 244: ...Index SIMOTION SCOUT 244 Configuration Manual 11 2016 ...