15 Operating Parameters
15.3 Administrative
254
SICAM MMU 7KG9663, Device Manual
E50417-H1040-C514-A3, Edition 01.2016
15.3.3
SICAM I/O Unit 7XV5673 (Subdevice)
1)
If you have selected the
no
option, no settings are possible.
Parameter
Default Setting
Setting Range
I/O Unit connected
no
no
1)
yes
Server IP address
192.168.0.56
Any
Server port
51000
10000 to 65535
Response time-out
3 * 10 ms
0 ms = invalid
10 ms to 60 000 ms
Source of output 1-N
Indication 3 from remote
-none-
Device OK
Battery Failure
Settings Load
Settings Check
Settings Activate
Modbus TCP OK
Ethernet Link Error
Time Synchronization Error
Primary NTP Server Error
Secondary NTP Server Error
Daylight Saving Time
Default IP Address
Limit Violation x (x = 1 to 16)
or user-defined names, see
Indication x from Remote (x = 1 to 8)
Rotating Field Clockwise
Group Indication x (x = 1 to 4)
IEC 60870-5-104 OK
Binary Input x-N I/O Unit (x = 1 to 3)
Binary Input x-P I/O Unit (x = 1 to 3)
External I/O Unit OK
Source of output 2-N
Indication 4 from remote
Source of output 3-N
Indication 5 from remote
Source of output 1-P
Indication 6 from remote
Source of output 2-P
Indication 7 from remote
Source of output 3-P
Indication 8 from remote