7 Operation
7.3 Configuration of the Device
100
SICAM MMU 7KG9663, Device Manual
E50417-H1040-C514-A3, Edition 01.2016
−
Pulse with retrigger
: This indication is output as pulse. The output pulse is retriggered if the
indication is changed during the pulse output. This means that the pulse output is extended.
Fig. 7-25
Pulse with Retrigger
✧
If you have selected one of the two
Pulse
types in the
Operating mode
list box, enter an output time x
(in x *10 ms) into the
Output time for pulse operating mode
field.
Behavior when Activating the Set of Parameters after the Set of Parameters was Changed
Persistent:
The binary output is set to the new status (ON or OFF) as defined by the current indication.
Pulse:
If the binary output is ON in
pulse
mode while activating the set of parameters, the binary output is
immediately switched to the OFF status after the set of parameters has been successfully activated.
This happens even if the parameterized
Output time for pulse operating mode
has not yet elapsed.
✧
After the parameterization click
Send
.
The parameters are transmitted to the device but not enabled yet (passive set of parameters).
✧
If you do not want to make any additional settings, continue with the
activation
of the device configuration
Activating the Set of Parameters
. If you want to change other settings, enter the changes
and then enable the device configuration as described in
Activating the Set of Parameters
.
Parameterizing an Energy Counter
✧
Select the desired parameters for an
indication
in the list boxes and option fields (see figure 7-21,
example terminal G1/2) as described in Table 7-3.
✧
After the parameterization click
Send
.
The parameters are transmitted to the device but not enabled yet (passive set of parameters).
✧
If you do not want to make any additional settings, continue with the
activation
of the device configuration
Activating the Set of Parameters
. If you want to change other settings, enter the changes
and then enable the device configuration as described in
Activating the Set of Parameters
.
Indication
Output
Output with retrigger
Binary output with
„Source inverted“ = no
ON
OFF
ON
OFF
Output time
Output time
Indication
Indication
Indication
Indication
Output
Output
Output
Output with
retrigger
Binary output with
„Source inverted“ = yes
Extended output time
ON
OFF
Extended output time
SICAM-MMU_7KG9663_US.book Page 100 Monday, December 7, 2015 12:22 PM