9 Communication
9.2 Modbus
161
SICAM MMU 7KG9663, Device Manual
E50417-H1040-C514-A3, Edition 01.2016
9.2.7.3
Register 0071 to 0089: Version Information
These registers are write protected. A write attempt will be rejected with exception code 03
(ILLEGAL_DATA_VALUE).
9.2.7.4
Register 0101 to 0102: Device Status
This register is write protected. A write attempt will be rejected with exception code 03
(ILLEGAL_DATA_VALUE).
Data type: indication
Table 9-6
Register 0071 to 0089: Version Information
Register
Type of Information
Remark
0071 to 0076
Boot version
e.g. „V01.10.01“
0077 to 0082
Firmware version
e.g. „V01.10.01“
0083 to 0089
Parameter set version
e.g. „V01.10.01“
Table 9-7
Register 0101 to 0102: Device Status
Register
Type of Information
Remark
0101/2
0
Device ready
1 = Device ready
0101/2
2
Battery failure
0 = Battery OK,
1 = Battery failure (exchange battery)
0101/2
4
Reserved
= 0
0101/2
6
Reserved
= 0
0101/2
8
Settings Load
1 = Load settings
0101/2
10
Settings Check
1 = Check settings
0101/2
12
Settings Activate
1 = Activate settings
0101/2
14
Reserved
= 0
0102/2
0
Rotating field clockwise
0 = Anti-clockwise
1 = Clockwise
0102/2
2
to
0102/2
14
Reserved
= 0
NOTE
Registers between 0103 and 0141 that are not shown can be read too during requests and return the value 0.