13 Technical Data
13.2 Test Data
233
SICAM MMU 7KG9663, Device Manual
E50417-H1040-C514-A3, Edition 01.2016
13.2
Test Data
Reference Conditions for Determining the Test Data
13.2.1
Electrical Tests
Standards
Insulation Test according to IEC 61010-1
Input current
Rated current ± 1 %
Input voltage
Rated voltage ± 1 %
Frequency
45 Hz to 65 Hz
Curve shape
Sine, total harmonic distortion
≤
5 %
Ambient temperature
23 °C ± 1 °C
Supply voltage
V
HN
± 1 %
Warm-up time
≥
15 min
Interfering fields
None
Standards:
IEC 60688 and IEC 60255
IEEE Std C37.90, see individual functions
VDE 0435
For more standards see also individual functions
Inputs/Outputs
Insulation
Rated
Voltage
ISO Test Voltage
Category
Current measuring inputs
Reinforced
150 V
AC 2.3 kV
Cat. III
Voltage measuring inputs
Reinforced
480 V
Surge voltage
9.76 kV
Cat. III
Supply voltage
Reinforced
300 V
DC 3.125 kV
Cat. III
Binary outputs
Reinforced
300 V
AC 3.536 kV
Cat. III
Ethernet interface
Function
< 50 V
DC 700 V
Cat. III
SICAM-MMU_7KG9663_US.book Page 233 Monday, December 7, 2015 12:22 PM