7 Operation
7.3 Configuration of the Device
104
SICAM MMU 7KG9663, Device Manual
E50417-H1040-C514-A3, Edition 01.2016
Parameterizing a Limit
To change for example limit 1, proceed as follows:
✧
In the navigation window, select the
Operational
menu, then the
Select automation functions
submenu
and click
Measurand limits 1-8
.
Fig. 7-28
Configure Tab, Measurand Limits 1-8 Input/output Window (Detail)
✧
Enter the desired values in the fields and select the parameters in the list boxes and option fields as
described in Table 7-5.
Hysteresis of Limit Violation
Fig. 7-29
Hysteresis (General Representation)
t
100 %
0%
Start
Start
End
End
Permissible
range
Limit Min
Limit Max
Hysteresis range