7 Operation
7.3 Configuration of the Device
106
SICAM MMU 7KG9663, Device Manual
E50417-H1040-C514-A3, Edition 01.2016
Rule for Linking Indications to a Group Indication
In a group indication, up to 4 indications can sequentially be linked logically. The indications 1 to 4 are always
linked successively as follows:
Indication 1 with Indication 2 = Indication 1/2
Indication 1/2 with Indication 3 = Indication 1/2/3
Indication 1/2/3 with Indication 4 = Group indication
Figure 7-30
Example: Linking 4 Indications to a Group Indication
Fig. 7-31
Example: Linking 2 Indications to a Group Indication
AND
AND
OR
INV
Group Indication 1
AND
INV
Group Indication 1
SICAM-MMU_7KG9663_US.book Page 106 Monday, December 7, 2015 12:22 PM