13 Technical Data
13.2 Test Data
234
SICAM MMU 7KG9663, Device Manual
E50417-H1040-C514-A3, Edition 01.2016
EMC Tests for Immunity (Type Tests)
EMC Test for Noise Emission (Type Test)
Standards:
IEC 60255-6 and -22, (product standards)
IEC/EN 61000-6-2
VDE 0435
For more standards see also individual
functions
1 MHz test, Class III, IEC 60255-22-1, IEC 61000-4-18,
IEEE C37.90.1
2.5 kV (peak); 1 MHz;
τ
= 15 µs;
400 Surges per s;
Test duration 2 s; R
i
= 200
Ω
Electrostatic discharge, Class III
IEC 60255-22-2, IEC 61000-4-2
4 kV contact discharge; 8 kV air discharge,
both polarities; 150 pF; R
i
= 330
Ω
Radio frequency electromagnetic field, amplitude-modulated,
Class III
IEC 61000-4-3, IEC 60255-22-3
10 V/m; 80 MHz to 2.7 GHz; 80 % AM;
1 kHz
Fast transient bursts, Class III
IEC 61000-4-4, IEC 60255-22-4, IEEE C37.90.1
2 kV; 5 ns/50 ns; 5 kHz;
Burst length = 15 ms;
Repetition rate 300 ms;
Both polarities;
R
i
= 50
Ω
;
Test duration 1 min
High energy surge voltages (SURGE), Installation Class III
IEC 61000-4-5, IEC 60255-22-5
Impulse: 1.2 µs/50 µs
Auxiliary voltage
Common mode: 2 kV; 12
Ω
; 9 µF
Diff. mode:1 kV; 2
Ω
; 18 µF
Measuring inputs, binary inputs and
relay outputs
Common mode: 2 kV; 42
Ω
; 0.5 µF
Diff. mode: 1 kV; 42
Ω
; 0,5 µF
HF on lines, amplitude-modulated, Class III
IEC 61000-4-6, IEC 60255-22-6
10 V; 150 kHz to 80 MHz; 80 % AM; 1 kHz
Power system frequency magnetic field
IEC 61000-4-8, Class IV;
30 A/m continuous; 300 A/m for 3 s
Standard:
IEC/EN 61000-6-4
Radio noise voltage to lines, only auxiliary voltage
IEC-CISPR 11
150 kHz to 30 MHz Limit Class B
Interference field strength
IEC-CISPR 11
30 MHz to 1000 MHz Limit Class B
SICAM-MMU_7KG9663_US.book Page 234 Monday, December 7, 2015 12:22 PM