14 Operational Indications
240
SICAM MMU 7KG9663, Device Manual
E50417-H1040-C514-A3, Edition 01.2016
Time Synchronization
Error
Error during the time synchroniza-
tion from the NTP server or fieldbus
Indication off: At least one time message was received
during the set timer ("
Error indication after
"). The time
stamp is set when the first valid time information or time
synchronization is received.
Indication on: No time message was received during the
set timer ("
Error indication after
").
The time stamp is set after the "
Error indication after
"
timer has expired and no synchronization message was
received.
Parameter range: see chapter 7.3.4.1
Error sources with RTC:
- no valid time after device startup
Error sources with NTP or fieldbus:
- „
Error indication after
" timer expires and no synchro-
nization message was received
Error during internal time synchro-
nization
Indication on: RTC time invalid
Indication off: After setting the clock via HTML (see
chapter 7.3.4.1)
During battery failure at device startup
Primary NTP Server
Error
Faulty or no response from the
primary NTP server
Indication on: Error
Indication off: Valid time messages has been received
for a period of 10 min
Only for time synchronization via Ethernet NTP (see
chapter 7.3.4.1)
Secondary NTP
Server Error
Faulty or no response from the sec-
ondary NTP server
Indication on: Error
Indication off: Valid time messages has been received
for a period of 10 min
Only for time synchronization via Ethernet NTP (see
chapter 7.3.4.1)
Daylight Saving Time
Switching between daylight saving
time/standard time
Indication on: Daylight saving time
Indication off: Standard time
Default IP Address
The IP-Addr. push-button has been
pressed for more than 3 s.
Indication on: IP-Addr. push-button was pressed
The device restarts and applies the default IP address.
Limit Violation x
(x = 1 to 16)
Indication that a parameterized lim-
iting value has been violated
Indication on: The limit of the monitored measured value
has been violated or no measured value is parameter-
ized as input of the limiting value.
Indication off: The limit of the monitored measured value
is not violated.
Message invalid: The monitored measured value is
invalid
(e.g. frequency at V < 15 % of V
rated
).
Indication
Description
Notes
SICAM-MMU_7KG9663_US.book Page 240 Monday, December 7, 2015 12:22 PM