15 Operating Parameters
15.3 Administrative
251
SICAM MMU 7KG9663, Device Manual
E50417-H1040-C514-A3, Edition 01.2016
1)
This parameter offers the possibility of a blocked transmission of several measured values, that change in
quick succession
.
The time delay starts when the first measured value modification occurs. All of the following measured value
changes, occurring within the time delay are sent together in a spontaneous measured value telegram after
the expiration of time delay.
If a measured value changes several times within this time, then only the last modification of this measured
value is transmitted.
2)
Only if
measured values transmission
=
cyclic
or
measured values transmission
=
cyclic and station
interrogation
is selected, the parameter is relevant.
Redundancy IEC 60870-5-104
(Parameter of connection 2)
Redundancy mode
-none-
-none-
IEC 60870-5-104
Equal connections
IEC 60870-5-104
or
Equal connections
Port number
2404
2000 to 65535
Response time-out (t1)
15 s
1 s to 255 s
time-out for superv. ACK in case of no
data msg. (t2)
10 s
1 s to 255 s
Test frames period (t3)
20 s
1 s to 255 s
Max. unacknowledged transmitted I
frames (k)
12
For information;
Values cannot be parameterized.
Max. received I frames before ACK (w)
8
Parameter
Default Settings
Setting Range