15 Operating Parameters
15.3 Administrative
249
SICAM MMU 7KG9663, Device Manual
E50417-H1040-C514-A3, Edition 01.2016
15.3.2
Ethernet Communication
15.3.2.1 General Settings
1)
After the parameter changes have been enabled, the device resets.
2)
After enabling the parameter changes, any currently active Modbus TCP connections will be closed. The
Modbus TCP client must later re-open these connections.
15.3.2.2 Ethernet Communication with Bus Protocol Modbus TCP
1)
After the parameter changes have been enabled, the device resets.
Parameter
Default Settings
Setting Range
IP Address
1)
192.168.0.55
Any
0.0.0.0 = DHCP
Subnet mask
1)
255.255.255.0
Any
Default gateway
1)
192.168.0.1
Any
Enable SNMP
no
no
yes
Bus protocol
Modbus TCP
-none-
2)
Modbus TCP
IEC 60870-5-104
Parameter
Default Settings
Setting Range
Use a user-port number
1)
no
no
yes
User-port number
1)
(can only be set when
Use a user-port
number
is parameterized with
yes
)
10000
10000 to 65535
Access rights for user port
(can only be set when
Use a user-port
number
is parameterized with
yes
)
Full
Full
Read only
Access rights for user port 502
Full
Full
Read only
Keep Alive time
10 s
0 s = switch off
1 s to 65 535 s
Communication supervision time
600 * 100 ms
0 s = none
100 ms to 6 553 400 ms