7 Operation
7.3 Configuration of the Device
88
SICAM MMU 7KG9663, Device Manual
E50417-H1040-C514-A3, Edition 01.2016
✧
Activate the modified configuration as described in chapter 7.3.1.3.
7.3.1.2
Open Configuration from File
If you have selected
Open configuration from file
in the
Configure
tab, you can open an already existing file
in a folder. Proceed as follows:
Fig. 7-12
Configure Tab, Open Configuration from File
✧
Click
Browse...
The
Choose file to Upload
dialog opens.
Fig. 7-13
Choose File
NOTE
You can edit the displayed factory settings, activate and use them as active set of parameters. The original fac-
tory settings are not overwritten and can be used at anytime.