15 Operating Parameters
15.2 Automation Functions
247
SICAM MMU 7KG9663, Device Manual
E50417-H1040-C514-A3, Edition 01.2016
15.2
Automation Functions
The following automation functions are available:
•
Measurand limits 1-8
•
Measurand limits 9-16
Measurand Limits 1-8 and 9-16
Parameter
Default Setting
Setting Range
Measurand
-none-
-none-
Va; Vb; Vc
Vab; Vbc; Vca
Ia; Ib; Ic
VN; Vavg
IN; Iavg
Pa; Pb; Pc; P
Qa; Qb; Qc; Q
Sa; Sb; Sc; S
cos
ϕ
(a); cos
ϕ
(b); cos
ϕ
(c); cos
ϕ
PFa; PFb; PFc; PF
ϕ
a;
ϕ
b;
ϕ
c;
ϕ
f
Vunbal
Iunbal
ϕ
ab V;
ϕ
ac V
Limit
0.00
-1 000 000 000 to 1 000 000 000 (unit)
Limit type
Lower
Lower
Upper
Hysteresis (%)
1.0
0.0 to 10.0
Violation indication
Limit Violation x
(x = 1 to 16)
The name of the limit value indication is
customizable.
SICAM-MMU_7KG9663_US.book Page 247 Monday, December 7, 2015 12:22 PM