Technical data
12.10 Motor Protection
3VL molded-case circuit breakers
174
System Manual, 03/2009, 110 0110 - 02 DS 01
12.10
Motor Protection
The following characteristic values in the relevant tables apply for the SENTRON VL circuit breakers
in motor protection with different trip classes:
●
Trip class ETU10M fixed
●
Trip class ETU30M adjustable
●
Trip class ETU40M adjustable
Circuit breakers for motor protection with fixed trip class ETU10M
L
I
Characteristic value of circuit breakers for
motor protection with fixed trip class
ETU10M
These circuit breakers possess an
adjustable overload and short-circuit release
and a fixed trip class.
They are current-limiting and have a phase
failure sensitivity feature
Table 12- 38 Circuit breakers for motor protection with fixed trip class ETU 10M
Max. rated power of the
motor at 50 Hz AC
[kW]
Circuit
breaker
Rated
current I
n
[A]
380 / 415 V
500 V
Adjustable range
of the overload
protection I
R
[A]
Adjustable
range of the
short-circuit
protection I
I
[A]
Trip
class TC
[s]
63
30
37
0.41-1.0 x I
n
1.25-11 x I
n
10
100
37. 45
55
0.41-1.0 x I
n
1.25-11 x I
n
10
VL160
160
55. 75
75. 90
0.41-1.0 x I
n
1.25-11 x I
n
10
200
90, 110
110, 132
0.41-1.0 x I
n
1.25-11 x I
n
10
VL250
250
132
160
0.41-1.0 x I
n
1.25-11 x I
n
10
315
160
200
0.41-1.0 x I
n
1.25-11 x I
n
10
VL400
315
200
250
0.41-1.0 x I
n
1.25-11 x I
n
10
VL630
500
250
355
0.41-1.0 x I
n
1. 5-12.5 x I
n
10
Содержание SENTRON 3VL series
Страница 2: ......
Страница 10: ...Table of contents 3VL molded case circuit breakers 10 System Manual 03 2009 110 0110 02 DS 01 ...
Страница 40: ...System overview 4 2 Key data 3VL molded case circuit breakers 40 System Manual 03 2009 110 0110 02 DS 01 ...
Страница 350: ...Correction sheet 3VL molded case circuit breakers 350 System Manual 03 2009 110 0110 02 DS 01 ...
Страница 358: ...Glossary 3VL molded case circuit breakers 358 System Manual 03 2009 110 0110 02 DS 01 ...
Страница 359: ......