Technical data
12.13 Undervoltage release connection data
3VL molded-case circuit breakers
180
System Manual, 03/2009, 110 0110 - 02 DS 01
12.13
Undervoltage release connection data
Maximum connection lengths of the undervoltage releases depending on V
n
The table below lists the maximum lengths for the connecting cables of the undervoltage
release family 1 (VL160X to VL400) and/or 2 (VL630 to VL1600). The values in the table
refer to 100% V
n
in the case of the undervoltage releases. A cable loss of 15% V
n
has been
taken into account.
Table 12- 44 Undervoltage release family 1
MLFB
Rated voltage in V
From-to
A = 0.5 mm
2
l
max
in m
A = 1 mm
2
l
max
in m
A = 1.5 mm
2
I
max
in m
3VL9400-1UN00
12
12
DC
0.93
1.85
2.78
3VL9400-1UP00
24
24
DC
3.66
7.32
10.98
3VL9400-1UU00
48
48
DC
11.79
23.57
35.36
3VL9400-1UV00
60
60
DC
21.98
43.97
65.95
3VL9400-1UR00
110
127
DC
99.59
199.17
298.76
3VL9400-1US00
220
250
DC
362.13
724.26
1086.40
3VL9400-1UD00
24
24
AC
1.78
3.57
5.35
3VL9400-1UG00
110
127
AC
41.00
82.01
123.01
3VL9400-1UM00
208
208
AC
97.18
194.35
291.53
3VL9400-1UH00
220
250
AC
153.40
306.80
460.20
3VL9400-1UQ00
277
277
AC
176.75
353.51
530.26
3VL9400-1UJ00
380
415
AC
438.14
876.28
1314.42
3VL9400-1UK00
440
480
AC
559.36
1118.72
1678.08
3VL9400-1UL00
525
550
AC
607.60
1215.21
1822.81
Содержание SENTRON 3VL series
Страница 2: ......
Страница 10: ...Table of contents 3VL molded case circuit breakers 10 System Manual 03 2009 110 0110 02 DS 01 ...
Страница 40: ...System overview 4 2 Key data 3VL molded case circuit breakers 40 System Manual 03 2009 110 0110 02 DS 01 ...
Страница 350: ...Correction sheet 3VL molded case circuit breakers 350 System Manual 03 2009 110 0110 02 DS 01 ...
Страница 358: ...Glossary 3VL molded case circuit breakers 358 System Manual 03 2009 110 0110 02 DS 01 ...
Страница 359: ......