Application planning
6.4 Use in DC systems
3VL molded-case circuit breakers
70
System Manual, 03/2009, 110 0110 - 02 DS 01
Setting range of the trip values
●
Thermal overload release:
Same setpoints as in 50 / 60 Hz networks.
●
Instantaneous short circuit trip unit:
The response threshold increases by 30 to 40%.
Example:
At the I
i
= 4000 A setting, the overcurrent trip unit responds at approx. 5200 A ± 20%.
Depending on the voltage, a series connection of 2, 3 or 4 current paths is required.
The following circuits are recommended since the current must flow through all current paths
in order to conform to the thermal tripping characteristic curves.
The thresold values of the instantaneous short-circuit release ("I" release) increase by 30 to
40%.
Suggested circuits for DC networks
Table 6- 2
Max. DC voltage Max. DC voltage for 3-pole circuit breakers
1)
for 4-pole circuit breakers
2)
6
5
4
3
2
1
L-
NSE0_00741a
L+
250 V DC
NSE0_01537
6
5
4
3
2
1
N
N
L-
L+
500 V DC
2-pole switching (non-grounded system)
If ground faults have been excluded or if every ground
fault is corrected immediately (ground fault monitoring),
the maximum permissible direct voltage can be 600 V
in both circuits.
6
5
4
3
2
1
L-
NSE0_00742a
L+
500 V DC
NSE0_01538
6
5
4
3
2
1
N
N
L-
L+
600 V DC
2-pole switching (grounded system)
The grounded pole should always be assigned to the
single conducting path so that if a short-circuit occurs,
2 conducting paths are always connected in series in
the case of 3-pole breakers, or 3 conducting paths in
the case of 4-pole breakers.
NSE0_00743a
6
5
4
3
2
1
L-
L+
600 V DC
NSE0_00744a
2
1
6
5
4
3
N
N
L-
L+
600 V DC
1-pole switching (grounded system)
The grounded pole is assigned to the ungrounded
conducting path.
1)
The max. direct voltage applies for the circuit breakers VL160 to VL630 with extremely
high switching capacity (L). Otherwise a conversion is necessary in accordance with the
permissible maximum voltage for 3 conducting paths, e.g. VL160X with switching capacity
"N" with factor 250V / 600 V = 0.42.
2)
In the case of 4 conducting paths in series, the 4th pole must be equipped either with a
100% trip unit or no trip unit at all. Moreover, the additional warming of the 4th conducting
path means the maximum operating current must be reduced by 25%, and the trip times of
the thermal overload release can change.
Содержание SENTRON 3VL series
Страница 2: ......
Страница 10: ...Table of contents 3VL molded case circuit breakers 10 System Manual 03 2009 110 0110 02 DS 01 ...
Страница 40: ...System overview 4 2 Key data 3VL molded case circuit breakers 40 System Manual 03 2009 110 0110 02 DS 01 ...
Страница 350: ...Correction sheet 3VL molded case circuit breakers 350 System Manual 03 2009 110 0110 02 DS 01 ...
Страница 358: ...Glossary 3VL molded case circuit breakers 358 System Manual 03 2009 110 0110 02 DS 01 ...
Страница 359: ......