![Siemens SENTRON 3VL series Скачать руководство пользователя страница 31](http://html.mh-extra.com/html/siemens/sentron-3vl-series/sentron-3vl-series_system-manual_382625031.webp)
System overview
4.2 Key data
3VL molded-case circuit breakers
System Manual, 03/2009, 110 0110 - 02 DS 01
31
Type
VL160X
3VL1
VL160
3VL2
VL250
3VL3
VL400
VL4
VL630
3VL5
VL800
VL6
VL1250
3VL7
VL1600
3VL8
Weights of 3-pole circuit breakers [kg]
•
Basic switch without
overcurrent trip unit
-
1.5
1.6
4.2
7.8
14.2
21
27.3
•
Thermomagnetic overcurrent
trip unit
-
0.7
0.7
1.5
1.2
-
-
-
•
Electronic overcurrent trip
unit
-
0.9
0.9
1.7
1.5
1.8
4.0
4.0
•
Basic switch with
thermomagnetic overcurrent
trip unit
2.0
2.2
2.3
5.7
9.0
-
-
-
•
Basic switch with electronic
overcurrent trip unit
-
2.4
2.5
5.9
9.3
16.0
25.0
31.3
Weights of 4-pole circuit breakers [kg]
•
Basic switch without
overcurrent trip unit
-
2.0
2.2
5.5
9.7
18.2
27.5
34.8
•
Thermomagnetic overcurrent
trip unit
-
1.0
1.0
1.9
1.5
-
-
-
•
Electronic overcurrent trip
unit
-
1.1
1.1
2.1
2.0
2.3
6.0
6.0
•
Basic switch with
thermomagnetic overcurrent
trip unit
2.5
3.0
3.2
7.4
11.2
-
-
-
•
Basic switch with electronic
overcurrent trip unit
-
3.1
3.3
7.6
11.7
20.5
33.5
40.8
Rated short-circuit breaking capacity in accordance with IEC 60947-2
See Chapter Technical overview (Page 145)
•
Service life make-break
operations
20000
20000
20000
20000
10000
10000
3000
3000
•
Service life electrical make-
break operations
10000
10000
10000
10000
5000
3000
1500
1500
•
Max. switching frequency
[1/h]
120
120
120
120
60
60
30
30
•
Connection types
See Chapter Connecting (Page 97)
Connection cross-sections
Box terminal
8)
•
Solid or stranded cable;
copper only [mm²]
2.5 to 95 2.5 to 95 25 to 185 50 to 300 -
-
-
-
•
Finely stranded with end
sleeve [mm²]
2.5 to 50 2.5 to 50 25 to 120 50 to 240 -
-
-
-
•
Flexible power rail [mm]
12 x 10
12 x 10
17 x 10
25 x 10
-
-
-
-
•
Terminal plate for flexible
power rail
7)
[mm]
-
-
-
-
Qty. 2
10 × 32
-
-
-
Содержание SENTRON 3VL series
Страница 2: ......
Страница 10: ...Table of contents 3VL molded case circuit breakers 10 System Manual 03 2009 110 0110 02 DS 01 ...
Страница 40: ...System overview 4 2 Key data 3VL molded case circuit breakers 40 System Manual 03 2009 110 0110 02 DS 01 ...
Страница 350: ...Correction sheet 3VL molded case circuit breakers 350 System Manual 03 2009 110 0110 02 DS 01 ...
Страница 358: ...Glossary 3VL molded case circuit breakers 358 System Manual 03 2009 110 0110 02 DS 01 ...