Technical data
12.6 Power loss
3VL molded-case circuit breakers
System Manual, 03/2009, 110 0110 - 02 DS 01
167
12.6
Power loss
Power loss for fixed-mounted circuit breakers
Thermomagnetic overcurrent trip units (TM)
The table below shows the power loss and the current path resistance for thermomagnetic
overcurrent trip units (TM). The power loss applies for I
n
with 3-phase balanced load. The
specified power loss is the sum of all current paths. The current path resistance is only a
guide value and can fluctuate.
Table 12- 29 Power loss for thermomagnetic overcurrent trip units (TM)
Type
Rated current [A]
Power loss [W]
Path resistance [mΩ]
16
11
14
20
17
14
25
7
3,7
32
11
3,6
40
16
3,3
50
15
2,0
63
18
1,5
80
24
1,3
100
22
0.73
125
31
0,66
VL160X
160
41
0,53
50
16
2,1
63
21
1,8
80
27
1,4
100
27
0,90
125
36
0,77
VL160
160
55
0,63
200
60
0,47
VL250
250
71
0,38
200
60
0,50
250
84
0,45
315
120
0,40
VL400
400
175
0,36
315
85
0,29
400
120
0,25
500
170
0,23
VL630
630
230
0,19
Содержание SENTRON 3VL series
Страница 2: ......
Страница 10: ...Table of contents 3VL molded case circuit breakers 10 System Manual 03 2009 110 0110 02 DS 01 ...
Страница 40: ...System overview 4 2 Key data 3VL molded case circuit breakers 40 System Manual 03 2009 110 0110 02 DS 01 ...
Страница 350: ...Correction sheet 3VL molded case circuit breakers 350 System Manual 03 2009 110 0110 02 DS 01 ...
Страница 358: ...Glossary 3VL molded case circuit breakers 358 System Manual 03 2009 110 0110 02 DS 01 ...
Страница 359: ......