Technical data
12.12 Undervoltage release
3VL molded-case circuit breakers
System Manual, 03/2009, 110 0110 - 02 DS 01
179
Table 12- 43 Undervoltage release for VL630 to VL1600
VL630
VL800
VL1250
VL1600
Operating voltage [V]
Drop (circuit breaker trips)
0.35-0.70 V
s
0.35-0.70 V
s
0.35-0.70 V
s
0.35-0.70 V
s
Pick-up (circuit breaker can be
switched on)
0.85-1.10 V
s
0.85-1.10 V
s
0.85-1.10 V
s
0.85-1.10 V
s
Power consumption
AC 50 / 60 Hz [VA]
110-127 V
220-250 V
208 V
277 V
380-415 V
440-480 V
500-525 V
1.1
2.1
2.2
1.6
2.0
2.3
2.9
1.1
2.1
2.2
1.6
2.0
2.3
2.9
1.1
2.1
2.2
1.6
2.0
2.3
2.9
1.1
2.1
2.2
1.6
2.0
2.3
2.9
DC [W]
12 V
24 V
48 V
60 V
110-127 V
220-250 V
1.2
1.4
1.5
1.6
1.2
1.5
1.2
1.4
1.5
1.6
1.2
1.5
1.2
1.4
1.5
1.6
1.2
1.5
1.2
1.4
1.5
1.6
1.2
1.5
Max. opening (release)
time [ms]
80
80
80
80
Содержание SENTRON 3VL series