Technical data
12.12 Undervoltage release
3VL molded-case circuit breakers
178
System Manual, 03/2009, 110 0110 - 02 DS 01
12.12
Undervoltage release
The undervoltage releases of the SENTRON VL circuit breakers have the following technical data:
Table 12- 42 Undervoltage releases for VL160X, VL160 to VL400
VL160X
VL160
VL250
VL400
Operating voltage [V]
Drop (circuit breaker trips)
0.35-0.70 V
s
0.35-0.70 V
s
0.35-0.70 V
s
0.35-0.70 V
s
Pick-up (circuit breaker can be
switched on)
0.85-1.10 V
s
0.85-1.10 V
s
0.85-1.10 V
s
0.85-1.10 V
s
Power consumption
AC 50 / 60 Hz [VA]
110-127 V
220-250 V
208 V
277 V
380-415 V
440-480 V
500-525 V
600 V
1.5
1.5
1.8
2.1
1.6
1.8
2.05
2.4
1.5
1.5
1.8
2.1
1.6
1.8
2.05
2.4
1.5
1.5
1.8
2.1
1.6
1.8
2.05
2.4
1.5
1.5
1.8
2.1
1.6
1.8
2.05
2.4
DC [W]
12 V
24 V
48 V
60 V
110-127 V
220-250 V
0.75
0.8
0.8
0.8
0.8
0.8
0.75
0.8
0.8
0.8
0.8
0.8
0.75
0.8
0.8
0.8
0.8
0.8
0.75
0.8
0.8
0.8
0.8
0.8
Max. opening (release)
time [ms]
50
50
50
50
Содержание SENTRON 3VL series
Страница 2: ......
Страница 10: ...Table of contents 3VL molded case circuit breakers 10 System Manual 03 2009 110 0110 02 DS 01 ...
Страница 40: ...System overview 4 2 Key data 3VL molded case circuit breakers 40 System Manual 03 2009 110 0110 02 DS 01 ...
Страница 350: ...Correction sheet 3VL molded case circuit breakers 350 System Manual 03 2009 110 0110 02 DS 01 ...
Страница 358: ...Glossary 3VL molded case circuit breakers 358 System Manual 03 2009 110 0110 02 DS 01 ...
Страница 359: ......