3VL molded-case circuit breakers
System Manual, 03/2009, 110 0110 - 02 DS 01
145
Technical data
12
12.1
Technical overview
The technical overview lists all the operating data and dimensions as well as the possible
overcurrent tripping methods and the switching capacities of the SENTRON VL circuit
breakers. The RCD blocks overview contains the relevant operating data.
Table 12- 1 Technical overview VL160X, VL160 to VL400
VL160X
VL160
VL250
VL400
Rated current at 50 °C ambient
temperature
16 to 160 A
26 to 160 A
80 to 250 A
125 to 400 A
Rated operating voltage V
e1)
(AC) 50-60 Hz [V]
690
690
690
690
Number of poles
3
4
3
4
3
4
3
4
(DC)
2)
[V]
500
500
600
600
600
600
600
600
$
%
'
&
mm A
mm B
mm C
mm D
105
157
87
107
139
157
87
107
105
175
87
107
139
175
87
107
105
175
87
107
139
175
87
107
139
279
106
138
183
279
106
138
Overcurrent trip unit
Thermomagnetic TM
X
X
X
X
X
X
X
X
Electronic trip unit ETU
LCD
--
--
--
--
X
X
X
X
X
X
Interchangeability
--
--
X
X
X
X
X
X
1)
Rated insulation voltage of the main conducting paths V
i
= 800 V AC
2)
Rated direct current data apply only for thermomagnetic overcurrent trip units. The values apply for at least 3 conductor
paths in series and extremely high switching capacity "L". For switching direct current, the maximum permissible direct
voltage per conductor path must be observed; see also "Suggested circuits for DC networks" in the Chapter "Application
planning".
Содержание SENTRON 3VL series
Страница 2: ......
Страница 10: ...Table of contents 3VL molded case circuit breakers 10 System Manual 03 2009 110 0110 02 DS 01 ...
Страница 40: ...System overview 4 2 Key data 3VL molded case circuit breakers 40 System Manual 03 2009 110 0110 02 DS 01 ...
Страница 350: ...Correction sheet 3VL molded case circuit breakers 350 System Manual 03 2009 110 0110 02 DS 01 ...
Страница 358: ...Glossary 3VL molded case circuit breakers 358 System Manual 03 2009 110 0110 02 DS 01 ...
Страница 359: ......