SCALANCE X204RNA SCALANCE X204RNA EEC (PRP)
Operating Instructions, , C79000-G8976-C294-03
15
Product characteristics
4
4.1
Overview of the product characteristics
Overview of the product characteristics
The SCALANCE X204RNA and the SCALANCE X204RNA EEC have the same functionality
and differ only in the environmental conditions, the input voltage ranges and the option of
using SFP modules with the SCALANCE X204RNA EEC.
Table 4- 1
Overview of the product characteristics
Device type SCALANCE
X204RNA
X204RNA EEC
SIMATIC environment
●
●
Diagnostics LED
●
●
24 VDC
●
-
24 V .. 250 VDC / 100 V .. 240 V AC
-
●
Housing
Plastic
Metal
2 x 24 VDC
●
-
100 Base-T, full duplex/half duplex
●/-
●/-
10 Base-T
-
-
Signaling c on-site operation
(set/reset button)
●
●
Diagnostics: Web, SNMP
●
●
C-PLUG
●
●
IRT capability
-
-
SNTP
●
●
Note
PROFINET controllers can communicate with PROFINET devices via the PRP network
(PROFINET IO and RT). In this case all PROFINET devices (controllers and devices) must
either be capable of PRP themselves or must be connected to the PRP network via a
RedBox.
Within a PRP network (A or B), PROFINET controllers and devices can also communicate
with each other as SANs (PROFINET IO, RT and IRT). A direct PROFINET communications
relation between DANPs and SANs is not supported.