UM353-1
Model Designation and Specifications
March 2003
14-11
14.9 ENVIRONMENTAL SPECIFICATIONS
14.9.1 Standard Mounting
Mounting, Typical Location ........................................Control room or other protected area
Temperature Limits:
Operating.......................................................0 to 50
°
C (32 to 122
°
F)
Storage ..........................................................-40 to 85
°
C (-40 to 185
°
F)
Climatic Conditions.....................................................IEC654-1 (Class B3)
Corrosive Conditions...................................................IEC 654-4 (Class 2)
14.9.2 Enclosure Mounting
Mounting:
Typical Location ...........................................Out-of-doors or other area without environmental controls
Enclosure.......................................................User supplied
Model 353 Case.............................................Installed inside enclosure
Model 353 Display........................................Exposed through enclosure to external environment
Installation Requirements..............................Refer to Section 8 Installation
Temperature Limits:
Enclosure Internal, Operating .......................0 to 50
°
C (32 to 122
°
F)
Enclosure External, Operating ......................-40 to 50
°
C (-40 to 122
°
F)
Controller Storage .........................................-40 to 85
°
C (-40 to 185
°
F)
Climatic Conditions:....................................................IEC654-1 (Class B3)
Corrosive Conditions:..................................................IEC654-4 (Class 2)
14.9.3 Electromagnetic Compatibility (EMC)
EN61326-1, 1998
EN61000-4-3 (EM Field)
EN50081-2 (Radiated Emissions)
EN61000-4-4 (EFT/Burst)
EN55011 (Conducted Emissions)
EN61000-4-5 (Surge)
EN61000-3-2 (Flicker)
EN61000-4-6 (Conducted RF)
EN61000-3-3 (Current Harmonics)
EN61000-4-8 (Magnetic Immunity)
EN61000-4-2 (ESD)
EN61000-4-11 (Voltage Dip/Short Interruption)
14.10 AGENCY APPROVALS
The Moore 353 has been designed to meet various agency approvals. Contact the factory or your local Siemens
(Process Industries Division) representative for current approvals. Labels on each Moore 353 list the agency
approvals that apply to that particular instrument.
FM/CSA
Class I, Division 2, Groups A, B, C, and D
CE - see Section 14.10.2
ABS TYPE Approval
StockCheck.com
Содержание Moore 353
Страница 2: ...S t o c k C h e c k c o m ...
Страница 14: ...Contents UM353 1 xii March 2003 S t o c k C h e c k c o m ...
Страница 24: ...Introduction UM353 1 March 2003 1 10 S t o c k C h e c k c o m ...
Страница 152: ...LonWorks Communications UM353 1 March 2003 5 4 S t o c k C h e c k c o m ...
Страница 164: ...Network Communications UM353 1 6 12 March 2003 S t o c k C h e c k c o m ...
Страница 246: ...Operation UM353 1 March 2003 9 8 S t o c k C h e c k c o m ...
Страница 254: ...Controller and System Test UM353 1 March 2003 10 8 S t o c k C h e c k c o m ...
Страница 282: ...Circuit Description UM353 1 March 2003 13 4 S t o c k C h e c k c o m ...
Страница 298: ...Model Designation and Specifications UM353 1 March 2003 14 16 S t o c k C h e c k c o m ...
Страница 302: ...Abbreviations And Acronyms UM353 1 15 2 March 2003 S t o c k C h e c k c o m ...
Страница 304: ...Warranty UM353 1 W 2 March 2003 S t o c k C h e c k c o m ...