Data Mapping
UM353-1
March
2003
7-24
Analog Indicator [ODA] - (V2.2)
Code
R/W
Description
Range
Coil(MB)
C/P (LIL)
L#P1AA
R
1-Process 1 Alarm A is Active
1/0
00296+48(#-1)
n+4/1(0)
L#P1AN
R/W
1-Process 1 Alarm A is Not Acknowledged
1/0
00297+48(#-1)
n+4/1(1)
L#P1AE
R/W
1-Process 1 Alarm A is Enabled
1/0
00298+48(#-1)
n+41(2)
L#P1BA
R
1-Process 1 Alarm B is Active
1/0
00299+48(#-1)
n+4/1(3)
L#P1BN
R/W
1-Process 1 Alarm B is Not Acknowledged
1/0
00300+48(#-1)
n+4/1(4)
L#P1BE
R/W
1-Process 1 Alarm B is Enabled
1/0
00301+48(#-1)
n+4/1(5)
L#P2AA
R
1-Process 2 Alarm A is Active
1/0
00302+48(#-1)
n+4/1(6)
L#P2AN
R/W
1-Process 2 Alarm A is Not Acknowledged
1/0
00303+48(#-1)
n+4/1(7)
L#P2AE
R/W
1-Process 2 Alarm A is Enabled
1/0
00304+48(#-1)
n+4/1(8)
L#P2BA
R
1-Process 2 Alarm B is Active
1/0
00305+48(#-1)
n+4/1(9)
L#P2BN
R/W
1-Process 2 Alarm B is Not Acknowledged
1/0
00306+48(#-1)
n+4/1(10)
L#P2BE
R/W
1-Process 2 Alarm B is Enabled
1/0
00307+48(#-1)
n+4/1(11)
L#OS1
R/W
1-Alarms - Out of Service
1/0
00308+48(#-1)
n+4/1(12)
L#PB1
R/W
PB1SW Input MD (*)
(V1.3)
1/0
00309+48(#-1)
n+4/1(13)
L#PB2
R/W
PB2SW Input MD (*)
(V1.3)
1/0
00310+48(#-1)
n+4/(14)
L#PB3
R/W
PB3SW Input MD (*)
(V1.3)
1/0
00311+48(#-1)
n+4/1(15)
L#P3AA
R
1-Process 3 Alarm A is Active
1/0
00312+48(#-1)
n+5/1(0)
L#P3AN
R/W
1-Process 3 Alarm A is Not Acknowledged
1/0
00313+48(#-1)
n+5/1(1)
L#P3AE
R/W
1-Process 3 Alarm A is Enabled
1/0
00314+48(#-1)
n+5/1(2)
L#P3BA
R
1-Process 3 Alarm B is Active
1/0
00315+48(#-1)
n+5/1(3)
L#P3BN
R/W
1-Process 3 Alarm B is Not Acknowledged
1/0
00316+48(#-1)
n+5/1(4)
L#P3BE
R/W
1-Process 3 Alarm B is Enabled
1/0
00317+48(#-1)
n+5/1(5)
L#P4AA
R
1-Process 4 Alarm A is Active
1/0
00318+48(#-1)
n+1/1(6)
L#P4AN
R/W
1-Process 4 Alarm A is Not Acknowledged
1/0
00319+48(#-1)
n+5/1(7)
L#P4AE
R/W
1-Process 4 Alarm A is Enabled
1/0
00320+48(#-1)
n+5/1(8)
L#P4BA
R
1-Process 4 Alarm B is Active
1/0
00321+48(#-1)
n+5/1(9)
L#P4BN
R/W
1-Process 4 Alarm B is Not Acknowledged
1/0
00322+48(#-1)
n+5/1(10)
L#P4BE
R/W
1-Process 4 Alarm B is Enabled
1/0
00323+48(#-1)
n+5/1(11)
L#OS
R/W
1-Alarms - Out of Service
1/0
00324+48(#-1)
n+5/1(12)
L#CC
R
1-Configuration has Changed 1/0
00325+48(#-1)
n+5/1(13)
L#NA
R/W
1-Unacknowledged Loop Event
1/0
00326+48(#-1)
n+5/1(14)
L#AE
R
1-Active Loop Event
1/0
00327+48(#-1)
n+5/1(15)
* These bits indicate the status of the switch input MD. A write of a “1” will have the same effect as pressing and
releasing the button on the faceplate. If the action of the switch is sustained the switch will change position. If
the action is momentary, the switch will close for one scan cycle.
StockCheck.com
Содержание Moore 353
Страница 2: ...S t o c k C h e c k c o m ...
Страница 14: ...Contents UM353 1 xii March 2003 S t o c k C h e c k c o m ...
Страница 24: ...Introduction UM353 1 March 2003 1 10 S t o c k C h e c k c o m ...
Страница 152: ...LonWorks Communications UM353 1 March 2003 5 4 S t o c k C h e c k c o m ...
Страница 164: ...Network Communications UM353 1 6 12 March 2003 S t o c k C h e c k c o m ...
Страница 246: ...Operation UM353 1 March 2003 9 8 S t o c k C h e c k c o m ...
Страница 254: ...Controller and System Test UM353 1 March 2003 10 8 S t o c k C h e c k c o m ...
Страница 282: ...Circuit Description UM353 1 March 2003 13 4 S t o c k C h e c k c o m ...
Страница 298: ...Model Designation and Specifications UM353 1 March 2003 14 16 S t o c k C h e c k c o m ...
Страница 302: ...Abbreviations And Acronyms UM353 1 15 2 March 2003 S t o c k C h e c k c o m ...
Страница 304: ...Warranty UM353 1 W 2 March 2003 S t o c k C h e c k c o m ...