UM353-1
Data Mapping
March 2003
7-43
7.3.12 Trend Data (Loop Defined by MLTP)
Included in MPU Controller board firmware version 1.30 and higher.
Code R/W Description Range Register
(MB) C/P
(LIL)
A1RMN
R
ATD01 MIN SCALE
Real
48001
n/a
A1RMX
R
ATD01 MAX SCALE
Real
48003
n/a
A1DPP
R
ATD01 Decimal Point Position
0-5
48005
n/a
A1EU
R
ATD01 Engineering Units
6 ASCII Char
48006
n/a
A1YR
R
ATD01 Year V2.0 (5)
1997-
48009
n/a
A1MT
R
ATD01 Month V2.0 (5)
1-12
48010
n/a
A1DY
R
ATD01 Day V2.0 (5)
1-31
48011
n/a
A1HR
R
ATD01 Hour V2.0 (5)
0-23
48012
n/a
A1MN
R
ATD01 Minute V2.0 (5)
0-59
48013
n/a
A1SC
R
ATD01 Second V2.0 (5)
0-59
48014
n/a
A1ST
R/W* ATD01 Sample Time x0.01=min 1-48000
48015
n/a
A1STC
R
ATD01 % Sample Time Complete 0-1000 (x.1=%)
48016
n/a
A1D1
R
ATD01 Data 1 (latest) 0-100%
128-3968
48017
n/a
A1D2
R
ATD01 Data 2 0-100%
128-3968
48018
n/a
A1D3
R
ATD01 Data 3 0-100%
128-3968
48019
n/a
....................................................................................................................................................................
A1D168
R
ATD01 Data 168 0-100%
128-3968
48184
n/a
A1D169
R
ATD01 Data 169 0-100%
128-3968
48185
n/a
A1D170
R
ATD01 Data 170 0-100%
128-3968
48186
n/a
* Writing to the sample time will reset all data points A1D1 through A1D170 to $0.
A2RMN
R
ATD02 MIN SCALE
Real
48201
n/a
A2RMX
R
ATD02 MAX SCALE
Real
48203
n/a
A2DPP
R
ATD02 Decimal Point Position
0-5
48205
n/a
A2EU
R
ATD02 Engineering Units
6 ASCII Char
48206
n/a
A2YR
R
ATD02 Year V2.0 (5)
1997
48209
n/a
A2MT
R
ATD02 Month V2.0 (5)
1-12
48210
n/a
A2DY
R
ATD02 Day V2.0 (5)
1-31
48211
n/a
A2HR
R
ATD02 Hour V2.0 (5)
0-23
48212
n/a
A2MN
R
ATD02 Minute V2.0 (5)
0-59
48213
n/a
A2SC
R
ATD02 Second V2.0 (5)
0-59
48214
n/a
A2ST
R/W* ATD02 Sample Time x0.01=min
1-48000
48215
n/a
A2STC
R
ATD02 % Sample Time Complete
0-1000 (x.1=%)
48216
n/a
A2D1
R
ATD02 Data 1 (latest) 0-100%
128-3968
48217
n/a
A2D2
R
ATD02 Data 2 0-100%
128-3968
48218
n/a
A2D3
R
ATD02 Data 3 0-100%
128-3968
48219
n/a
....................................................................................................................................................................
A2D168
R
ATD02 Data 168 0-100%
128-3968
48384
n/a
A2D169
R
ATD02 Data 169 0-100%
128-3968
48385
n/a
A2D170
R
ATD02 Data 170 0-100%
128-3968
48386
n/a
* Writing to the sample time will reset all data points A2D1 through A2D170 to $0.
StockCheck.com
Содержание Moore 353
Страница 2: ...S t o c k C h e c k c o m ...
Страница 14: ...Contents UM353 1 xii March 2003 S t o c k C h e c k c o m ...
Страница 24: ...Introduction UM353 1 March 2003 1 10 S t o c k C h e c k c o m ...
Страница 152: ...LonWorks Communications UM353 1 March 2003 5 4 S t o c k C h e c k c o m ...
Страница 164: ...Network Communications UM353 1 6 12 March 2003 S t o c k C h e c k c o m ...
Страница 246: ...Operation UM353 1 March 2003 9 8 S t o c k C h e c k c o m ...
Страница 254: ...Controller and System Test UM353 1 March 2003 10 8 S t o c k C h e c k c o m ...
Страница 282: ...Circuit Description UM353 1 March 2003 13 4 S t o c k C h e c k c o m ...