Data Mapping
UM353-1
March
2003
7-30
Digital Indicator Loop Status Word (
L#SW1
) - channel n/parameter 1
BIT Description
Value
Block
Read/Write
Output
0
Group 1 - Press PB1
1/0 (write of 1 presses PB)
ODP
W
1
Group 1 - Press PB2
1/0 (write of 1 presses PB)
ODP
W
2
Group 1 - Auto/Man Switch
1 - Auto 0- Manual (*)
ODP
R/W
3
Group 1 - Feedback Status
1 - True 0- False
ODP
R
4
Group 2 - Press PB1
1/0 (write of 1 presses PB)
ODP
W
5
Group 2 - Press PB2
1/0 (write of 1 presses PB)
ODP
W
6
Group 2 - Auto/Man Switch
1 - Auto 0- Manual (*)
ODP
R/W
7
Group 2 - Feedback Status
1 - True 0- False
ODP
R
8
Group 3 - Press PB1
1/0 (write of 1 presses PB)
ODP
W
9
Group 3 - Press PB2
1/0 (write of 1 presses PB)
ODP
W
10
Group 3 - Auto/Man Switch
1 - Auto 0- Manual (*)
ODP
R/W
11
Group 3 - Feedback Status
1 - True 0- False
ODP
R
12
Group 4 - Press PB1
1/0 (write of 1 presses PB)
ODP
W
13
Group 4 - Press PB2
1/0 (write of 1 presses PB)
ODP
W
14
Group 4 - Auto/Man Switch
1 - Auto 0- Manual (*)
ODP
R/W
15
Group 4 - Feedback Status
1 - True 0- False
ODP
R
Digital Indicator Loop Status Word (
L#SW2)
- channel n+1/parameter 1
BIT Description
Value
Block
Read/Write
Output
0
Group 5 - Press PB1
1/0 (write of 1 presses PB)
ODP
W
1
Group 5 - Press PB2
1/0 (write of 1 presses PB)
ODP
W
2
Group 5 - Auto/Man Switch
1 - Auto 0- Manual (*)
ODP
R/W
3
Group 5 - Feedback Status
1 - True 0- False
ODP
R
4
Group 6 - Press PB1
1/0 (write of 1 presses PB)
ODP
W
5
Group 6 - Press PB2
1/0 (write of 1 presses PB)
ODP
W
6
Group 6 - Auto/Man Switch
1 - Auto 0- Manual (*)
ODP
R/W
7
Group 6 - Feedback Status
1 - True 0- False
ODP
R
8
Group 7 - Press PB1
1/0 (write of 1 presses PB)
ODP
W
9
Group 7 - Press PB2
1/0 (write of 1 presses PB)
ODP
W
10
Group 7 - Auto/Man Switch
1 - Auto 0- Manual (*)
ODP
R/W
11
Group 7 - Feedback Status
1 - True 0- False
ODP
R
12
Group 8 - Press PB1
1/0 (write of 1 presses PB)
ODP
W
13
Group 8 - Press PB2
1/0 (write of 1 presses PB)
ODP
W
14
Group 8 - Auto/Man Switch
1 - Auto 0- Manual (*)
ODP
R/W
15
Group 8 - Feedback Status
1 - True 0- False
ODP
R
* A mask on command will toggle the position of the Auto/Man switch
StockCheck.com
Содержание Moore 353
Страница 2: ...S t o c k C h e c k c o m ...
Страница 14: ...Contents UM353 1 xii March 2003 S t o c k C h e c k c o m ...
Страница 24: ...Introduction UM353 1 March 2003 1 10 S t o c k C h e c k c o m ...
Страница 152: ...LonWorks Communications UM353 1 March 2003 5 4 S t o c k C h e c k c o m ...
Страница 164: ...Network Communications UM353 1 6 12 March 2003 S t o c k C h e c k c o m ...
Страница 246: ...Operation UM353 1 March 2003 9 8 S t o c k C h e c k c o m ...
Страница 254: ...Controller and System Test UM353 1 March 2003 10 8 S t o c k C h e c k c o m ...
Страница 282: ...Circuit Description UM353 1 March 2003 13 4 S t o c k C h e c k c o m ...
Страница 298: ...Model Designation and Specifications UM353 1 March 2003 14 16 S t o c k C h e c k c o m ...
Страница 302: ...Abbreviations And Acronyms UM353 1 15 2 March 2003 S t o c k C h e c k c o m ...
Страница 304: ...Warranty UM353 1 W 2 March 2003 S t o c k C h e c k c o m ...