
Controller and System Test
UM353-1
March
2003
10-4
10.1.6 Alarms
Upon power up, FCO101 has 4 alarms enabled:
•
Hi alarm at 110% on AIN1
•
Lo alarm at -10% on AIN1
•
Deviation alarm of 110% between AIN1 and SETPT
•
No alarm
1. Press the ALARM/STEP DOWN button to step through the Alarm limits and Enable/Disable Status. Notice all
the alarms are enabled and the alarm limits are displayed in engineering units on the numeric display and as a
percentage of range by a flashing LED on the S bargraph. If security clearance is satisfied, the alarm limits can
be changed by rotating the pulser knob. Try changing the alarm limit A1 to 50% (300 DEG F) and press
STORE to save the new value.
2. Press EXIT to return to normal operation mode.
3. Enter manual mode to display Loop01.V.
4. Turn the pulser knob until both the valve output and process input are greater than 50%. Note that the
alphanumeric display will flash “A1 HI” and the L and S LEDs will flash. Press the ACK button to
acknowledge the alarm.
Alarms have a default priority of 3 (see Alarm block in Section 3.2), meaning that the alarms must be acknowledged
to clear the flashing. Alarms may also be configured as self clearing. Try changing the alarm priority to 4 using the
Configuration Road Map in Section 2 or the following steps:
1. Press ENTER/EXIT CONF. LOOP should be displayed.
2. Press STEP DOWN twice until VIEW appears on the display.
3. Press the right arrow button 3 times or turn the pulser knob until EDIT FB appears on the display.
4. Press STEP DOWN. A/M will be displayed.
5. Press the right arrow button 3 times or the turn pulser knob until ALARM appears on the display.
6. Press STEP DOWN to display RG PTR
7. Press the right arrow button or turn the pulser knob until A1 PRIOR appears on the display.
8. Press STEP DOWN to display 3 on the numeric display.
9. To change the priority of alarm 1 from 3 to 4, rotate the pulser knob until 4 appears on the numeric display.
10. Press STORE to save the configuration change.
11. Press ENTER/EXIT CONF to return to normal operation.
Try adjusting the process above and below 50% (300 DEG F). Notice that the alarm will clear without pressing the
ACK button if the process drops below the alarm limit - deadband. Use the ALARM QUICK button to return the
Alarm Limit A1 to the default 110% (540 DEG F) and press STORE to save. Other alarm parameters referenced in
the ALARM function block description may be changed in a similar manner.
StockCheck.com
Содержание Moore 353
Страница 2: ...S t o c k C h e c k c o m ...
Страница 14: ...Contents UM353 1 xii March 2003 S t o c k C h e c k c o m ...
Страница 24: ...Introduction UM353 1 March 2003 1 10 S t o c k C h e c k c o m ...
Страница 152: ...LonWorks Communications UM353 1 March 2003 5 4 S t o c k C h e c k c o m ...
Страница 164: ...Network Communications UM353 1 6 12 March 2003 S t o c k C h e c k c o m ...
Страница 246: ...Operation UM353 1 March 2003 9 8 S t o c k C h e c k c o m ...
Страница 254: ...Controller and System Test UM353 1 March 2003 10 8 S t o c k C h e c k c o m ...
Страница 282: ...Circuit Description UM353 1 March 2003 13 4 S t o c k C h e c k c o m ...
Страница 298: ...Model Designation and Specifications UM353 1 March 2003 14 16 S t o c k C h e c k c o m ...
Страница 302: ...Abbreviations And Acronyms UM353 1 15 2 March 2003 S t o c k C h e c k c o m ...
Страница 304: ...Warranty UM353 1 W 2 March 2003 S t o c k C h e c k c o m ...