Factory Configured Options
UM353-1
March
2003
4-6
4.4 FCO104 - External Set Controller with Non-Tracking Local Setpoint
Factory Configured Option FCO104 provides a single loop controller with external setpoint configured in Loop01.
A block diagram of the loop configuration is shown below along with any
changes
to the default parameter values
of the configured blocks. If the loop tag ‘LOOP01’ is changed, all configured references will automatically be
changed to the new tag.
PB2SW
PS
E/I
O1
SE
SI
IS
ES
NC
NO
MD
ST
E
I
IO
AIN2
QS
O1
External Setpoint
SETPT
TV
TC
O1
AIN1
QS
O1
AOUT1
QS
ALARM
A1
A2
A3
A4
A/M
O1
AS
NA
MS
ES
SS
PID
O1
AE
AW
SR
P
D
A
TV
TC
EM
S
D
P
S
F
A
I
LU
LD
Valve
Process
P
V
LOOP01
0.00-100.00 PRCT
0.00-100.00 PRCT
0.00-100.00 PRCT
X
DOUT1
S
DOUT2
S
S
IRev. 2)
PB2SW - PB2 Switch Function Block
INPUT MD - Input MD ------- Loop01.E/I.SE
ESN - Exec. Seq. No. ---------- 5
ALARM - Alarm Function Block
RG PTR - Range Pointer ------- Loop01.AIN1.OR
INPUT P - Input P -------------- Loop01.AIN1.O1
INPUT D - Input D ------------- Loop01.E/I.O1
ESN - Exec. Seq. No. ---------- 20
PID - PID Controller Function Block
RG PTR - Range Pointer ----------- Loop01.AIN1.OR
INPUT P - Input P ------------------ Loop01.AIN1.O1
INPUT S - Input S ------------------ Loop01.E/I.O1
INPUT F - Input F ------------------ Loop01.A/M.O1
INPUT A - Input A ----------------- Loop01.A/M.AS
INPUT I - Input I ------------------- Loop01.E/I.ES
ESN - Exec. Seq. No.--------------- 25
E/I - Ext/Int Transfer Switch Function Block
INPUT ST - Input ST -------------- Loop01.PB2SW.PS
INPUT E - Input E ------------------ Loop01.AIN2.O1
INPUT I - Input I ------------------- Loop01.SETPT.O1
ESN - Exec. Seq. No. -------------- 15
A/M - Auto/Manual Function Block
RG PTR - Range Pointer ---------- Loop01.PID.OR
INPUT A - Input A ----------------- Loop01.PID.O1
ESN - Exec. Seq. No. -------------- 30
SETPT - Setpoint Function Block
RG PTR - Range Pointer ---------- Loop01.AIN1.OR
ESN - Exec. Seq. No. -------------- 10
AOUT1 - Analog Output 1 Function Block
RG PTR - Range Pointer ------------ Loop01.PID.OR
INPUT S - Input S ------------------- Loop01.A/M.O1
StockCheck.com
Содержание Moore 353
Страница 2: ...S t o c k C h e c k c o m ...
Страница 14: ...Contents UM353 1 xii March 2003 S t o c k C h e c k c o m ...
Страница 24: ...Introduction UM353 1 March 2003 1 10 S t o c k C h e c k c o m ...
Страница 152: ...LonWorks Communications UM353 1 March 2003 5 4 S t o c k C h e c k c o m ...
Страница 164: ...Network Communications UM353 1 6 12 March 2003 S t o c k C h e c k c o m ...
Страница 246: ...Operation UM353 1 March 2003 9 8 S t o c k C h e c k c o m ...
Страница 254: ...Controller and System Test UM353 1 March 2003 10 8 S t o c k C h e c k c o m ...
Страница 282: ...Circuit Description UM353 1 March 2003 13 4 S t o c k C h e c k c o m ...
Страница 298: ...Model Designation and Specifications UM353 1 March 2003 14 16 S t o c k C h e c k c o m ...
Страница 302: ...Abbreviations And Acronyms UM353 1 15 2 March 2003 S t o c k C h e c k c o m ...
Страница 304: ...Warranty UM353 1 W 2 March 2003 S t o c k C h e c k c o m ...