/RQJHUFDEOHOHQJWKV
If you want to implement cable lengths above those permitted in a segment, you
must use RS485 repeaters. Information on this topic can be found in the
RS485 repeater product information.
/HQJWKRIWKHVWXEFDEOHV
If bus nodes are connected to a bus segment via stub cables (e.g. PG via a normal
PG cable), then you must consider the maximum possible length of the stub cable.
The following table lists the maximum permitted lengths of stub cables per
segment:
Table 5-26
Stub cable lengths per segment
1XPEHURIQRGHVZLWKVWXEFDEOHOHQJWK
RI
7UDQVPLVVLRQUDWH 0D[OHQJWKRIVWXE
FDEOHVSHUVHJPHQW
PRUP
0
9.6 kbps to 93.75
kbps
M 96
32
32
187.5 kbps
M 75
32
25
500 kbps
M 30
20
10
1.5 Mbps
M 10
6
3
3 Mbps to 12 Mbps
1)
1)
1)
1)
At 3 Mbps and higher, use the PG patch cord (Order No. 6ES7 901-4BD00-0XA0) to
connect the PG or PC. You can use multiple PG patch cords of this number in an
installation. Do not use any other type of stub cable.