S7-300 Automation System, Hardware and Installation: CPU 31xC and CPU 31x
11-24
A5E00105492-03
6WDWLRQ6WDWXV
Table 11-15 Structure of station status 3 (byte 2)
%LW
'HVFULSWLRQ
0 to 6
These bits are always “0”
7
The incoming diagnostic messages exceeds the memory capacity of the DP slave.
The DP master cannot write all diagnostic messages sent by the DP slave to its diagnostic
buffer.
0DVWHU352),%86DGGUHVV
The "Master PROFIBUS address" diagnostic byte stores the DP address of the DP
master:
•
that has configured the DP slave and
•
has read and write access to the DP slave.
Table 11-16 Structure of the master PROFIBUS address (byte 3)
%LW
'HVFULSWLRQ
0 to 7 DP address of the DP master that has configured the DP slave and has read/write access to
that DP slave.
FFH: DP slave was not configured by a DP master
YHQGRU,'
The vendor ID contains a code specifying the DP slave's type.
Table 11-17 Structure of the vendor ID (byte 4, 5)
%\WH
%\WH
9HQGRU,'IRUWKH&38
80
H
EE
H
CPU 315-2 DP
80
H
F0
H
CPU 317-2 DP
80
H
D0
H
313C-2-DP
80
H
D1
H
314C-2-DP
Содержание CPU 312
Страница 10: ... RQWHQWV S7 300 Automation System Hardware and Installation CPU 31xC and CPU 31x x A5E00105492 03 ...
Страница 76: ... RQILJXULQJ S7 300 Automation System Hardware and Installation CPU 31xC and CPU 31x 5 50 A5E00105492 03 ...
Страница 146: ... RPPLVVLRQLQJ S7 300 Automation System Hardware and Installation CPU 31xC and CPU 31x 9 34 A5E00105492 03 ...
Страница 232: ... ORVVDU S7 300 Automation System Hardware and Installation CPU 31xC and CPU 31x 13 16 A5E00105492 03 ...