7HVWLQJ)XQFWLRQV'LDJQRVWLFVDQG)DXOW(OLPLQDWLRQ
S7-300 Automation System, Hardware and Installation: CPU 31xC and CPU 31x
11-14
A5E00105492-03
(YHQWUHFRJQLWLRQ
The table below shows how CPU 31x-2 operating as DP master recognizes
operating mode transitions of a CPU operating as DP slave or data exchange
interruptions.
Table 11-8
Event recognition by CPUs 31x-2 as the DP master
(YHQW
:KDWKDSSHQVLQWKH'3VODYH"
Bus failure interrupt
(short-circuit,
connector unplugged)
•
Calls OB86 with the message
6WDWLRQIDLOXUH
(incoming
event; diagnostic address of Slot 0 of the DP slave that is
assigned to the DP master)
•
with I/O access: Call of OB122 (I/O access error)
DP slave: RUN
→
STOP
•
Call of OB82 with the message
0RGXOHHUURU
(incoming event; diagnostic address of Slot 2 of the DP slave
that is assigned to the DP master; Variable
OB82_MDL_STOP=1)
DP slave: STOP
→
RUN
•
Call of OB82 with the message
0RGXOH2.
(outgoing event; diagnostic address of Slot 2 of the DP slave
that is assigned to the DP master; Variable
OB82_MDL_STOP=0)
(YDOXDWLRQLQWKHXVHUSURJUDP
The table below shows how you can, for example, evaluate RUN to STOP
transitions of the DP slave in the DP master.
Table 11-9
Evaluation in the DP master of RUN to STOP transitions by the DP slave
,QWKH'3PDVWHU
,QWKH'3VODYH&38['3
Diagnostic addresses: (Example)
Master diagnostic address =
Slave diagnostic address =
(Slot 0 of slave)
(Diagnostic) address for "Slot 2"=
(Slot 2 of slave)
Diagnostic addresses: (Example)
Slave diagnostic address =
Master diagnostic address = irrelevant
The CPU calls OB82 with the following
information:
•
OB82_MDL_ADDR:=
•
OB82_EV_CLASS:=B#16#39 (incoming
event)
•
OB82_MDL_DEFECT: = Module error
Tip: The CPU diagnostic buffer also contains
this information
In the user program you should also include
SFC 13 "DPNRM_DG" for reading out DP
slave diagnostic data.
←
CPU: RUN -> STOP
The CPU generates a DP slave
diagnostics message frame
Содержание CPU 312
Страница 10: ... RQWHQWV S7 300 Automation System Hardware and Installation CPU 31xC and CPU 31x x A5E00105492 03 ...
Страница 76: ... RQILJXULQJ S7 300 Automation System Hardware and Installation CPU 31xC and CPU 31x 5 50 A5E00105492 03 ...
Страница 146: ... RPPLVVLRQLQJ S7 300 Automation System Hardware and Installation CPU 31xC and CPU 31x 9 34 A5E00105492 03 ...
Страница 232: ... ORVVDU S7 300 Automation System Hardware and Installation CPU 31xC and CPU 31x 13 16 A5E00105492 03 ...